Vermont Casting 2465 Side Wall Termination Assembly, Install the Vent Adapter Pipe, 30001935

Models: 2466 2465

1 36
Download 36 pages 36.52 Kb
Page 15
Image 15
Side Wall Termination Assembly

Install the Vent Adapter Pipe

(Simpson Dura-Vent Components)

1.Install the Restrictor Plate. Consult the ‘Vent Run Specifications’ on Page 8 to determine whether the restrictor plate is needed. If so, put the restrictor plate in place within the inner flue collar. (Fig. 16)

2.Discard the inner starter pipe shipped with the log- set. Using the starter pipe assembly listed on Page 7, slide the inner section out to allow access.

• Run a bead of sealant around the bottom end of the starter pipe and attach the assembly to the stove using three 1/4-20 x 3/8” Phillips screws provided in the parts bag. (Fig. 20)

3.Install the Outer Adapter Pipe. Apply a 1/4” bead of cement around the outside surface, about one inch from the crimped end. (Fig. 21) Orient the verti- cal seam to the rear, and insert the crimped end of the outer pipe into the flue collar. Fasten with three sheet metal screws provided.

Inner Adapter

1/4-20 x 3/8Pipe

Phillips Screws

ST762

Fig. 20 Simpson DuraVent - install inner adapter pipe.

ST763

Fig. 21 Simpson DuraVent - install outer adapter pipe.

30001935

Dutchwest Direct Vent / Natural Vent Gas Heater

Side Wall Termination Assembly

1.Locate the vent opening on the wall. Refer to Fig- ure 5, Page 6, to determine the opening centerline. It may be necessary to first position the stove and measure to find the hole location. Depending on whether the wall is made of combustible materials, cut the opening to the size shown in Figure 22. Com- bustible wall openings must be framed as shown in Figure 22.

CFM System

9³⁄

 

 

 

 

 

 

(240 mm

 

9³⁄

 

 

 

(240 mm

 

 

 

DuraVent

Combustible Wall

Framing Detail

System

 

10”

 

 

 

 

 

(250 mm)

 

10”

 

 

7¹⁄

(250 mm)

 

(191 mm)

VO584-100

Fig. 22 Locate vent opening.

2.Measure the wall thickness and cut the wall sleeve sections to proper length (MAXIMUM 12”). Assemble the sleeve with the #8 sheet metal screws supplied. Attach the firestop plate to the sleeve end with the holes. (Fig. 23) NOTE: The wall sleeve is required in combustible walls only.

3.Install the Wall Firestop/Sleeve assembly into the wall cutout and fasten the firestop to the wall cutout framing members. (Fig. 23)

12”

 

(305 mm)

Sleeve

Max. Length

Firestop

ZCS103

Fig. 23 Assemble the wall sleeve and firestop.

 

 

15

Page 15