TO USE THE VENT GRAPH

TO USE THE VENT GRAPH

1.Determine the height of the centre of the horizontal vent pipe exiting through the outer wall. Using this dimension on the Sidewall Vent Graph (Fig. 12 ), locate the point it intersects with the slanted graph line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.Select the indicated dimension, and position the fire- place in accordance with same.

EXAMPLE A:

If the vertical dimension from the floor of the fireplace is 11 feet (335cm) the horizontal run to the face of the outer wall must not exceed 14 feet (427cm).

EXAMPLE B:

If the vertical dimension from the floor of the fireplace is 7 feet (214cm), the horizontal run to the face of the outer wall must not exceed 8-1/2 feet (259cm).

SIDEWALL VENTING GRAPH

(Dimensions in Feet)

For D232

30

 

29

 

28

 

27

 

26

 

25

 

24

 

23

 

22

 

21

 

20

 

19

 

18

 

17

 

16

 

15

 

14

 

13

 

12

eg: A

11

 

10

 

9

 

8

 

7

eg: B

6

 

 

5

 

4

 

3

 

TOTHE CENTRE

VERTICALDIMENSION

OFTHE HORIZONTAL

FROMTHE FLOOROF

VENTPIPE

THEFIREPLACE

3

4

5

6

7

8

9

10 11

12

13 14 15

16

17

18 19 20

HORIZONTAL DIMENSION

SEE PAGE 13 & 14 FOR VENTING REQUIREMENTS FOR SNORKELS.