run if the vertical exceeds 24".

Ensure sidewall venting clearances are observed.

If installing a snorkel a minimum 24" vertical rise is necessary. The maximum horizontal run with the 24" vertical pipe is 36" (915mm). This measurement is taken from the collar of the fireplace to the face of the exterior wall. See vent graph for extended horizontal

DO NOT BACK FILL AROUND SNORKEL. SOIL SHOULD NOT BE LESS THAN 4" BELOW SNORKEL.

run if the vertical exceeds 24".

1.

Establish vent hole through the wall (Fig. 13,14 & 15).

2.

Remove soil to a depth of approximately 16" below

 

base of snorkel. Install drain pipe. Install window well

 

(not supplied). Refill hole with 12" of coarse gravel

 

leaving a clearance of approximately 4" below snorkel.

 

See Fig. 22.

3.

Install vent system.

FOUNDATION

RECESS

WATERTIGHT

SEAL

AROUND

PIPE

SNORKEL

WALL

SCREWS

SHEET METAL

Fig. 23

SCREWS

4.

Ensure a watertight seal is made around the vent pipe

 

coming through the wall.

5.

Apply high temperature sealant caulking (supplied)

 

around the 4 and 7 inch snorkel collars.

6.

Slide into vent pipe and secure to the wall.

7.

Level the soil so as to maintain a 4" clearance below

 

snorkel. See Fig. 22.

FIRESTOP

SNORKEL

 

7" PIPE

SCREWS

4" CLEARANCE

 

 

GROUND

 

WINDOW WELL

 

GRAVEL

24"/608mm

DRAIN

MINIMUM*

 

 

FOUNDATION WALL

*A minimum of 24"/608mm vertical pipe must be installed when using the snorkel kit.

*The 22" vertical rise (center to center) of the snorkel may be included for calculation of max. horizontal run.

Fig. 22

- 14 -

If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fasten brackets to wall first and then secure to snorkel with self drilling #8 x 1/2 sheet metal screws. It will be necessary to extend the vent pipes out as far as the protruding wall face (Fig. 22).

VERTICAL THROUGH THE ROOF

APPLICATIONS

MAXIMUM

10 FT

(305cm)

MINIMUM

8FT./

MAXIMUM 40 FT.

VERTICAL

RISE

PIPE STRAPS

EVERY 3’

(92cm)

Fig. 24

This Gas Fireplace has been approved for,

a)Vertical installations up to 40 feet (12 metres) in height. Up to a 10 ft. horizontal vent run can be installed within the vent system using a maximum of two 90o elbows. (Fig. 24)

b)Up to two 45o elbows may be used within the horizontal run. For each 45o elbow used on the horizontal level the maximum horizontal length must be reduced by 18 inches.

Example: Maximum horizontal length

 

0

-

45o elbows

10 ft.

1

-

45o elbows

8.5 ft.

2

-

45o elbows

7 ft.

Page 14
Image 14
Vermont Casting D232 installation instructions Vertical Through The Roof Applications, run if the vertical exceeds