Vermont Casting DTV38s2 Gas Specifications, Gas Inlet and Manifold Pressures, High Elevations

Models: DTV38s2

1 48
Download 48 pages 55.3 Kb
Page 8
Image 8

Chateau™ Direct Vent Gas Fireplace

Gas Specifications

 

 

Gas

Max.

Min.

 

 

Input

Input

Model

Fuel

Control

BTU/h

BTU/h

DVT38S2IN

Natural Gas

AF-4034 w/

56,000

38,000

DVT38S2IP

Propane

7.5 DC Hi/Lo

 

 

56,000

45,500

Gas Inlet and Manifold Pressures

 

Natural

LP (Propane)

Minimum Inlet Pressure

5.5” w.c.

11.0” w.c.

Maximum Inlet Pressure

14.0” w.c.

14.0” w.c.

Manifold Pressure

3.5” w.c.

10.0” w.c.

 

 

 

High Elevations

Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4,500 feet (1,370m) above sea level.

For elevations above 4,500 feet (1,370m) in USA, installations must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having jurisdiction.

In Canada, please consult provincial and/or local authorities having jurisdiction for installations at elevations above 4,500 feet (1,370m).

WARNING: Improper installation, adjust- ment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.

Gas Line Installation

When purging gas line the front glass must be removed.

A gas shut off valve must be installed on the gas pipe line going into the appliance within easy access.

The gas pipeline can be brought in through the top of the valve box assembly.

The gas line connection can be made with properly tinned 1/2” copper tubing or 1/2” gas tight. Some municipalities have additional local codes, it is always best to consult your local authority and the CSA-B149.1installation codes.

For USA installations consult the current National Fuel Gas Code, ANSI Z223.1/NFPA 54.

1/2” NPT X 1/2” Flare

Shut-off Valve

 

 

1/2” Gas Tight or

 

 

Tinned Copper

 

 

(from valve)

FP297A

1/2” Gas Supply

(Not provided)

 

 

Fig. 6 Typical gas supply installation.

Always check for gas leaks with a mild soap and water solution applied with a brush no larger than 1” (25 mm). Never apply soap and water solution with a spray bottle. Do not use an open flame for leak testing.

The fireplace valve must not be subjected to any test pressures exceeding 1/2 psi. Isolate or disconnect this or any other gas appliance control from the gas line when pressure testing.

The gas control is equipped with an inlet and manifold pressure test point, therefore it is not necessary to pro- vide an 1/8” test point up stream of the control.

When using copper, use only approved fittings. Always provide a union when using black iron pipe so the gas line can be easily disconnected for burner servicing. A union may not be behind a wall. (Fig. 6) See the gas specifications for pressure details and ratings.

Electrical Junction Box

The fireplace, when installed, must be elec- trically connected and grounded in accord- ance with local codes or, in the absence of local codes, with the current CSA C22.1 Canadian Electrical Code or the national electrical code ANSI/NFPA No. 70 in the USA.

It is strongly suggested that the wiring of the Electrical Junction Box be carried out by a licensed electrician. The box should be near the valve box assembly to plug the cord into.

Ensure the power to the supply line has been disconnected before commencing this procedure.

8

20011957