Vermont Casting DTV38s2 Sidewall Installation, Step, Chateau Direct Vent Gas Fireplace, 20011957

Models: DTV38s2

1 48
Download 48 pages 55.3 Kb
Page 19
Image 19

When the vent termination exits through foundations less than 20” (508 mm) below siding outcrop, the vent pipe must be flush with the siding.

It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length of vent pipe from the flue collar of the fire- place to the face of the outer wall.

Horizontal plane means no vertical rise exists on this portion of the vent assembly.

 

20’ (6m)

 

 

 

Unitized Elbow

 

 

 

(SK890)

 

 

 

 

 

Pipe

 

 

 

Straps

(4.3m)

 

 

Every 3’

Pipe Straps

(914mm)

 

Every 3’

 

 

14’

 

 

(914mm)

Firestop/Zero

 

 

Minimum 2’

Clearance Sleeve

 

 

 

 

(610mm) Section

 

NOTE: Apply high temperature sealant or UL approved high temperature metal adhesive tape as directed on Page

16.

FP1453

Fig. 15 Support straps for horizontal runs.

The maximum number of 90° elbows per side wall installation is three (3), but must not have two (2) consecutive elbows in the horizontal plane.

A minimum of 2’ (610 mm) vertical section off the top of the unit is required, an elbow and a 1’ (305 mm) maximum horizontal run to get through a wall. (Fig. 16)

The maximum number of 45° elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run. (Fig. 16)

3'

(914mm)

Chateau™ Direct Vent Gas Fireplace

 

A

10'

B

 

(3m)

 

 

A + B = 17' (5.2m)

FP1238b

Fig. 17 Maximum vent run with elbows.

For each 90° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 36” (914 mm).

The maximum number of elbow degrees in a system is 270°. (Fig. 17)

Example:

 

 

 

 

 

 

 

 

 

 

Elbow 1

=

 

90°

 

 

 

 

 

Elbow 2

=

 

45°

4

 

Elbow 3

=

 

45°

 

 

 

 

 

Elbow 4

=

 

90°

 

 

 

 

Total angular variation =

270°

 

 

 

 

 

 

 

 

1

 

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP1455

Fig. 18 Maximum number of elbow degrees.

2'

(610mm)

C Wall Opening

L

6'9���"

Sidewall Installation

STEP 1

Locate vent opening on the wall. It may be necessary

(2080mm)

FP1454

Fig. 16 Minimum vertical run / maximum horizontal run.

For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18” (45 cm). This does not apply if the 45° elbows are installed on the vertical part of the vent system.

to first position the fireplace and measure to obtain hole location. Depending on whether the wall is combustible or noncombustible, cut opening to size. (Fig. 19)

For combustible walls first frame in opening.

Combustible Walls: Cut a 16¹⁄”H x 16¹⁄” W (413 x 413 mm) hole through the exterior wall and frame as shown.

Noncombustible Walls: Hole opening must be 11¹⁄” (286 mm) in diameter.

20011957

19

Page 19
Image 19
Vermont Casting DTV38s2 installation instructions Sidewall Installation, Step, Chateau Direct Vent Gas Fireplace, 20011957