Encore 1450 Non-Catalytic Woodburning Stove

Air must be able to flow between the wall and the shield. At least 50% of the bottom 1" (25 mm) of the shield should be open and the shield must be open at the top. Use metal screening, as in Figure 14, to keep stray objects from falling behind the shield.

The shield for a top-exit stove must extend 10"

(254 mm) above the top of the stove; for a rear exit configuration, the shield must be 36” (914 mm) high. The shield for the chimney connector must be 30” (762

mm)wide, centered behind the pipe; for installations that use an approved prefabricated chimney to pass through the ceiling, the chimney connector shield must stop 1” (25 mm) below the ceiling.

Air Flow

 

Metal

 

Screening

 

Wall Shield

 

Stud Wall

 

Framing

 

Noncombustible

 

Spacer and

Wall

Fasteners

Shield

 

 

Metal Lathe or

Drywall

Noncombustible

Spacers

 

Airflow

 

 

ST248

Fig. 14 Approved wall shield construction.

Chimney Connector Heat Shields

Chimney Connector Heat Shields should be used when it is necessary to protect nearby combustibles from the heat of the connector. The ceiling above horizontal runs of chimney connector must be protected as well if the clearance is inadequate.

In top-exiting installations, the connector shield must extend to a point exactly 36” (914 mm) above the flue collar or to an elbow in the connector, whichever is less. If the top-exiting connector extends to the ceiling where it connects with a prefabricated insulated metal chim- ney, an additional ceiling heat shield must be installed that is 24” (610 mm) in diameter and that extends 1” (25

mm)below the ceiling. The ceiling shield must be con- structed of 24 gauge or heavier sheet metal, and must be centered on the chimney.

Fireplace Mantel and Trim Shields

A fireplace installation requires special clearance be- tween the side of the stove and the right and left walls, between the side of the stove and the decorative side trim on the fireplace face, and between the top of the stove and the mantel.

Noncombustible shields installed 1” (25 mm) from the combustible surface on noncombustible spacers, called ventilated shields, may be used to reduce clearances.

To protect a mantel from the heat of an Encore in a fireplace installation, use a custom-made ventilated mantel shield that is at least 48” (1219 mm) long, that is centered over the stove. (Fig. 15) Ventilated shields for side trim must extend the full length of the trim.

An unprotected mantel (“A”, Fig. 16) cannot be more than 9 (229 mm) deep and must have a minimum clear- ance of 38” (965 mm), measured from the stove’s top plate. With a ventilated shield, this clearance may be reduced safely to 22” (559 mm).

Unprotected top trim (B) protruding 3/4” (19 mm) or less from the face of the fireplace must be a minimum of 27” (686 mm) from the stove’s top surface. With a ventilated trim shield, this clearance may be reduced safely to 20” (508 mm).

Unprotected side trim (C) that protrudes 3/4” (19 mm) or less from the face of a fireplace must have a minimum clearance of 10” (254 mm), measured from the stove’s top side edge. If the trim extends more than 3/4” (19 mm), it is subject to the requirements for wall clearance.

The charts and sample installations that follow list all the clearances required for the various installation con- figurations of the Encore.

1" (25mm)

1/4" (6mm)

ST501

Fig. 15 A custom formed mantel shield.

12

30002425

Page 12
Image 12
Vermont Casting Encore NC 1450 installation instructions Chimney Connector Heat Shields, Fireplace Mantel and Trim Shields