Vermont Casting NVC36 Attic Installation, Ceiling Installation, Venting Runs, NVC Series B-Vent

Models: NVC39 NVC36 NVC43

1 28
Download 28 pages 55.09 Kb
Page 9
Image 9
Attic Installation

Attic Installation

Firestop position when area above ceiling is an attic.

Ceiling InstallationNVC Series B-Vent Nails (4)

Venting Runs Firestop

Spacer

pipe.) Joist

Ceiling Installation

Firestop position when area above ceiling is NOT an attic.

(Firestop/draftstop appearances may vary. Only 1 firestop required per frame.)

FP384

Fig. 9 Firestop/draftstop positions.

 

 

 

 

 

 

 

NVC Series B-Vent

Venting Runs

 

 

 

 

 

 

 

 

Horizontal Run (in feet)

 

 

pipe.)

3

4

5

6

7

8

9

10

11

12

40

 

 

 

 

 

 

 

 

 

vent

 

 

 

 

 

 

 

 

 

 

38

 

A

 

 

 

 

 

 

feet)(inRun

oftocenterhorizontal

26

 

 

 

 

 

 

 

36

 

 

 

 

 

 

 

 

 

34

 

B

 

 

 

 

 

 

 

 

32

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

28

 

 

 

 

 

 

 

 

Vertical

unitoffloor

24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

18

 

 

 

 

 

 

 

 

 

from

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Measured

= Acceptable venting configuration

14

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

feet)(inRun = Unacceptable venting configuration

A: Vertical installations up to 40 feet (12m) in height. Up to a 8 ft. horizontal vent run can be installed within the vent system using a maximum of two 90-degree elbows or four 45-degree elbows.

B: Vertical installations up to 40 feet (12m) in height. Up to a 12 ft. horizontal vent run can be

installed within the vent system using a

 

maximum of two 45-degree elbows.

FP567a

Table 1 Venting configurations.