Vermont Casting NVC39 Start, Troubleshooting, NVC Series B-Vent, Nova SIT 820 Standing Pilot

Models: NVC39 NVC36 NVC43

1 28
Download 28 pages 55.09 Kb
Page 17
Image 17
Nova SIT 820 Standing Pilot

NVC Series B-Vent

Troubleshooting

Nova SIT 820 Standing Pilot

START

Gas Supply On

YES

CHECK

NO START Supply Line Hooked Up

Shutoff Valve Open

Pilot Lights With Piezo Ignitor

YES

Pilot Stays Lit

YES

Pilot Lights Main Burner

YES

System Ok.

CHECK NO Manual background

Manual backgroundManual background NO Manual background

Manual backgroundManual background NO Manual background

Lockout Has Engaged. Wait 60 Seconds and Try Again. Piezo Nut Tight for Good Ground. For Spark at Electrode While Depressing Piezo (Red Button)

-1/8" Gap to Pilot Hood Needed. All Wiring Connections Replace Piezo Ignitor

Check thermodisk

For Air in the Lines Thermopile Needs a Minimum 325Mv. Adjust Pilot Flame Height. All Wiring Connections.

Replace Thermopile Thermocouple Needs a Minimum of 14Mv.

Valve is Turned On

Wall Switch is Not Turned On. Watch for Grounded Wires! Thermopile Needs a Minimum 325Mv.

Plugged Burner Orifice. Defective Valve. Turn to Pilot, Meter Should Read Greater Than 100 Mv. If Not, Replace.

FP396

20000194

17

Page 17
Image 17
Vermont Casting NVC39, NVC36, NVC43 Start, Troubleshooting, NVC Series B-Vent, Nova SIT 820 Standing Pilot, Check, 20000194