Vermont Casting RDVOD 3390 manual Termination Clearances, Venting Requirements - Natural Vent Only

Models: RDVOD 3360 RDVOD 3369 RDVOD 3354 RDVOD 3350 RDVOD 3399 RDVOD 3390

1 40
Download 40 pages 19.6 Kb
Page 11
Image 11
Termination Clearances

Radiance Direct Vent /Natural Vent Gas Heater

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

Inside Corner

 

Outside Corner

 

 

A =

 

 

B =

A

 

 

Combustible

Combustible

 

 

6"(152mm)

 

6"(152mm)

 

V

Noncombustible

 

Noncombustible

2"(50mm)

 

 

V

2"(50mm)

 

B

 

Balcony -

 

Balcony -

 

 

with no side wall

 

with perpendicular side wall

G

H

 

 

 

V

 

V

G =

Combustible &

J

 

Noncombustible

 

Combustible &

 

H = 24"(610mm)

 

Noncombustible

 

12"(305mm)

J = 20"(508mm)

 

 

 

Recessed Location

 D D Venting Requirements - Natural Vent Only

CVenting RunsManual backgroundC

Manual background E Manual background

V

C = Maximum depth of 48" (1219mm) for recessed location.

D = Minimum width for back wall of a recessed location. Combustible 38"(965mm) Noncombustible 24"(610mm)

E = Clearance from corner in recessed location. Combustible 6"(152mm) Noncombustible 2"(50mm)

584-15

Fig. 10 Termination clearances.

Venting Requirements - Natural Vent Only

Vertical Run (in feet) (Measured from top of the unit before any elbow)

��

��

�� Manual backgroundA

�� Manual background B

��

��

��

��

��

��

��

��

��

��

������������������������������������������������������

Venting Runs

NOTE: When venting staight vertical, without any elbow, a minimum of 8 ft. vertical is required off the top of the stove.

Manual background = Acceptable venting configuration Manual background = Unacceptable venting configuration

A:Vertical installations up to 36 feet (12m) in height. Up to an 18 ft. horizontal vent run can be installed within the vent system using a maximum of two 90-degree elbows or four 45-degree elbows.

B:Vertical installations up to 36 feet (12m) in height. Up to a 24 ft. horizontal vent run can be installed within the vent system using a maximum of two 45-degree elbows.

(Ratio = 2/3, Hor./Vert.)

Horizontal Run (in feet)

 

Fig. 11 Vent termination window - Natural Vent ONLY.

NOTE: When using the FSDHAG, the restrictor

 

plate supplied with the stove is not used.

20004188

11

Page 11
Image 11
Vermont Casting RDVOD 3390 manual Termination Clearances, Venting Requirements - Natural Vent Only, Venting Runs, D Cc E