Radiance Direct Vent /Natural Vent Gas Heater
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
Inside Corner |
| Outside Corner |
| |
| A = |
|
| B = |
A |
|
| Combustible | |
Combustible |
|
| 6"(152mm) | |
| 6"(152mm) |
| V | Noncombustible |
| Noncombustible | 2"(50mm) | ||
|
| |||
V | 2"(50mm) |
| B |
|
Balcony - |
| Balcony - |
|
|
with no side wall |
| with perpendicular side wall |
G | H |
|
|
| |
V |
| V |
G = | Combustible & | J |
| ||
Noncombustible |
| |
Combustible & |
| |
H = 24"(610mm) |
| |
Noncombustible |
| |
12"(305mm) | J = 20"(508mm) |
|
|
|
Recessed Location
D
CC
E
V
C = Maximum depth of 48" (1219mm) for recessed location.
D = Minimum width for back wall of a recessed location. Combustible 38"(965mm) Noncombustible 24"(610mm)
E = Clearance from corner in recessed location. Combustible 6"(152mm) Noncombustible 2"(50mm)
Fig. 10 Termination clearances.
Venting Requirements - Natural Vent Only
Vertical Run (in feet) (Measured from top of the unit before any elbow)
��
��
�� A
�� B
��
��
��
��
��
��
��
��
��
��
�
�
�
�
������������������������������������������������������
Venting Runs
NOTE: When venting staight vertical, without any elbow, a minimum of 8 ft. vertical is required off the top of the stove.
= Acceptable venting configuration = Unacceptable venting configuration
A:Vertical installations up to 36 feet (12m) in height. Up to an 18 ft. horizontal vent run can be installed within the vent system using a maximum of two
B:Vertical installations up to 36 feet (12m) in height. Up to a 24 ft. horizontal vent run can be installed within the vent system using a maximum of two
(Ratio = 2/3, Hor./Vert.)
Horizontal Run (in feet) |
|
Fig. 11 Vent termination window - Natural Vent ONLY. | NOTE: When using the FSDHAG, the restrictor |
| plate supplied with the stove is not used. |
20004188 | 11 |