Vermont Casting RDVOD 3360 manual Injector Orifice Size Matrix, Air Shutter Adjustment, All Models

Models: RDVOD 3360 RDVOD 3369 RDVOD 3354 RDVOD 3350 RDVOD 3399 RDVOD 3390

1 40
Download 40 pages 19.6 Kb
Page 32
Image 32
All Models

Radiance Direct Vent/Natural Vent Gas Heater

All Models

22.Replace burner. Slide the burner in at an angle with left side lower than the right side. Slide the left side onto the injectors, making sure the burner leg remains at a 90° angle to the base. Lower the right hand side down in to place. Make sure the burner is as far left as possible and the injector shoulders are inside the burner.

NOTE: It is very critical to keep the left burner leg, which holds the injectors, at a 90° angle to the base.

Center

Plunger

Blue - NGRed - LP

Motor Top Cap

Valve

LOCAL

FP1037b

(Fig. 61) This keeps the orifices aligned with the tubes inside burner. Failure to do so could affect the flame appearance and performance of the unit.

22.Place conversion label on valve.

23.Reinstall the right and left log bracket assembly.

24.Reinstall the rear log bracket.

25.Replace logs.

26.Replace glass and stove front.

Conversion is complete.

Fig. 60 Depress and turn center plunger.

Left Burner Leg

Injector Orifices

90°

ST353a

Fig. 61 Remove and replace injector orifices.

Table 1. Injector Orifice Size Matrix

 

 

Conversion to Natural Gas

Input (BTU/h)

Kit #

Front

 

Part #

Rear

Part #

Minimum

Maximum

000-5002

#51

 

30000449

#40

20004263

25,000

35,000

 

 

000-5009

 

 

 

 

 

 

 

 

 

Conversion to LP

 

Input (BTU/h)

Kit #

Front

Part #

Rear

Part #

Minimum

Maximum

000-5003

#57

20004587

#54

20000130

27,500

35,000

 

000-5010

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 2. Air Shutter Adjustment

Model

Natural Gas

LP

RDVOD, RDVOD with

 

 

Vermont Castings Draft Hood Z31D00 FSDHAG

1”

Fully Closed

 

 

 

Minimum rear injector air inlet openings.

3232

20004188

Page 32
Image 32
Vermont Casting RDVOD 3360 Injector Orifice Size Matrix, Air Shutter Adjustment, All Models, Conversion to Natural Gas