IMPORTANT SAFETY INFORMATION
WARNING - Not following these instructions may cause severe injury or death to persons.
IMPORTANT INSTALLATION INSTRUCTIONS Continued
6.Controls intended for user activation must be located at least six feet (6’) away from any mov- ing part of the gate and where the user is prevented from reaching over, under, around or through the gate to operate the controls. Outdoor or easily accessible controls shall have a secu- rity feature to prevent unauthorized use.
7.The Stop and/or Reset button must be located in the
8.All warning signs and placards must be installed where visible in the area of the gate. A minimum of two placards shall be installed. A placard is to be installed in the area of each side of the gate and be visible to persons located on the side of the gate on which the placard is installed.
9.For gate operators utilizing a
a)See instructions on the placement of
b)Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle, trips the sensor while the gate is still moving, and
c)One or more
d)Use only Omron
10.For a gate operator utilizing a contact sensor (Edge sensor or like) in accordance with section 31.1.1 of the UL325 standard:
a)One or more contact sensors shall be located where the risk of entrapment or obstruction exists, such as at the leading edge, trailing edge, and post mounted both inside and outside of a vehicular horizontal slide gate (refer to page 7).
b)One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate.
c)One or more contact sensors shall be located at the pinch point of a vehicular vertical pivot gate.
d)A hardwired contact sensor shall be located and its wiring arranged so that the communication between the sensor and the gate operator is not subjected to mechanical damage.
e)A wireless contact sensor such as one that transmits radio frequency (RF) signals to the gate operator for entrapment protection functions shall be located where the transmission of the signals are not obstructed or impeded by building structures, natural landscaping or similar obstruction. A wireless contact sensor shall function under the intended
f)One or more contact sensors shall be located on the inside and outside leading edge of a swing gate. Additionally, if the bottom edge of a swing gate is greater than 6 inches (152 mm) above the ground at any point in its arc of travel, one or more contact sensors shall be located on the bottom edge (refer to page 7).
g)One or more contact sensors shall be located at the bottom
edge of a vertical barrier (arm).
h)Use only Miller Edge Model MGR20 or MGS20 edge sensor to comply with UL325
TECHNICAL SUPPORT 1 800 908 0884 | 3 |