7b Start-up — operate boiler (continued)

GOLD CGs-4E Gas-Fired Water Boiler — Boiler Manual

7b Start-up — operate boiler (continued)

If you discover evidence of any gas leak, shut down the boiler at once. Find the leak source with bubble test and repair immediately. Do not start boiler again until cor- rected. Failure to comply could result in severe personal injury, death or substantial property damage.

Check burner flames

View pilot and main flames through the inspection port in the Air inlet

box front cover.

Pilot burner flame (Figure 16)

PROPER pilot flame characteristics

1.Blue flame.

2.Inner cone engulfing pilot flame sensor.

3.Pilot flame sensor glowing cherry red.

IMPROPER pilot flame characteristics:

1.Overfired — Large flame lifting or blowing past pilot flame sensor.

2.Underfired — Small flame. Inner cone not engulfing pilot flame sen- sor.

3.Lack of primary air — Yellow flame tip.

4.Incorrectly heated pilot flame sensor.

Figure 16  Typical pilot burner flame

Figure 17  Typical main burner flame

Main burner flame (Figure 17)
PROPER main burner flame characteristics

1. Yellow-orange streaks may appear (caused by dust).

(NOTE: The CGs-4E will operate at low fire for the first 60 seconds.)

IMPROPER main burner flame characteristics

1.Overfired — Large flames.

2.Underfired — Small flames.

3.Lack of primary air — Yellow tipping on flames (sooting will occur).

Part number 550-110-282/1108

29