GOLD CGs-4E Gas-Fired Water Boiler — Boiler Manual

3d Piping — low temp systems (continued)

Figure 10 Boiler-bypass piping

Figure 11 Boiler-bypass piping

Zoning with circulators

Zoning with zone valves

Alternative to primary/secondary piping

(Alternative to primary/secondary piping

Figures 8 and 9)

Figures 8 and 9)

1Boiler isolation (balancing) valves

2Flow/check valve

3System or zone circulator

4System temperature gauges

5Zone valve

6Drain valve

7System temperature valves (see instructions to the left for adjusting valves)

8Blend temperature gauge

9Relief valve

10Automatic air vent (with diaphragm-type expan- sion tank), or connect to tank fitting (closed-type expansion tank). DO NOT use an automatic air vent when using closed-type expansion tank. It would allow air to leave the system, causing wa- terlogging of the expansion tank.

11Fill valve

12Diaphragm-type or bladder-type expansion tank, if used (For closed-type expansion tank, pipe from top of air separator to tank fitting as in Figure 5, page 15.)

13Air separator and automatic vent, if used (Note that the fill valve must always be connected to the expansion tank, regardless of location of expansion tank, circulator or air separator.)

Part number 550-110-282/1108

21

Page 21
Image 21