RPC-4840NRemotePowerController;User'sGuide

8.Test Boot Commands: When the RPC-4840N is powered up, both switched circuits will be set in the ON (closed) position. In order to test for proper operation, you may wish to perform the following test. Note that it is not necessary to connect a device to either switched circuit in order to perform this test.

a)Reboot Circuits: To initiate a boot cycle at both circuits, go to the RPC> command prompt, type /BOOT * and press [Enter]. Power to both circuits will be switched OFF. After the Boot Delay Period (Default = 5 Seconds), the power to both circuits will then be automatically switched back ON. Note that the Circuit Status Indicators on the RPC front panel will also switch Off and On.

b)Switch Circuits OFF: To switch both circuits OFF, go to the RPC> command prompt, type /OFF * and then press [Enter]. Power to both circuits will be switched OFF. Note that the Circuit Status Indicators will also be switched Off.

c)Switch Circuits ON: To switch both circuits ON, go to the RPC> command prompt, type /ON * and then press [Enter]. Power to both circuits will be switched ON. Note that the Circuit Status Indicators will also be switched On.

9.Exit Command Mode: Type /X and press [Enter] to exit from the RPC Command Mode, or disconnect using your Telnet program.

This completes the introductory overview of the RPC-4840N. Prior to installing and operating the unit, please review the remainder of this User's Guide for important information regarding safety considerations, as well as more detailed installation, configuration, and operation instructions.