Whirlpool T-K1S installation manual Natural Gas Supply Piping, Propane Supply Piping

Models: T-K1S

1 26
Download 26 pages 41.53 Kb
Page 8
Image 8

Gas Supply Piping

Check the rating plate to make sure that the unit was built for the type of gas available in the area. The gas supply piping should be sized according to the Applicable Plumbing Code for a maximum draw of 190,000 BTUH. First determine the effective length of the gas supply line by measuring the actual length of piping, and then adding 5 ft. for every elbow or “Tee” to the actual length. Use the charts below to determine the pipe diameter necessary to accommodate the BTU demand of the unit. If there are more than one gas drawing appliances on the line, size according to the maximum amount of BTU demand. The gas supply pressures must be within the ranges of the following chart:

Natural Gas

Min. 5” WC

Supply Pressure

Max. 10.5” WC

Propane Gas

Min. 11” WC

Supply Pressure

Max. 14” WC

Insufficient gas supply pressure can cause the Flash Water Heater to lose efficiency or not work at all.

WARNING: Fire or explosion may result if the maximum supply pressures are exceeded. The manifold gas pressure should be at maximum 2.6” WC for natural gas, and 3.4” WC for propane.

Always use approved connectors to connect the unit to the gas line. Always purge the gas line of any debris before connecting to the water heater.

WARNING: Conversion of this unit from natural gas to propane or propane to natural gas cannot be done in the field. Contact your local retailer or distributor to get the correct unit for your gas type. Always install a manual shutoff valve on the gas supply line in case of an emergency, or if service or maintenance is necessary.

This appliance and its individual shut-off valve must be isolated from the gas supply piping system by unplugging the unit and turning off the main gas valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ PSI.

When all of the connections have been made, check the gas line for leaks. Apply soapy water to all gas fittings and connections, if bubbles form, there may be a leak.

Natural Gas Supply Piping

Based on 0.60 specific gravity for natural gas at .5” WC pressure drop

DOE standard is 1100 BTU per cubic ft. of natural gas

Pipe

 

 

 

 

Cubic Feet of Natural Gas

 

 

 

 

 

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Length

10’

20’

30’

40’

50’

60’

70’

80’

90’

100’

125’

150’

200’

½”

174

119

96

82

73

66

61

56

53

50

44

40

34

¾”

363

249

200

171

152

138

127

118

111

104

93

84

72

1”

684

470

377

323

286

259

239

222

208

197

174

158

135

1 ¼”

1404

965

775

663

588

532

490

456

428

404

358

324

278

1 ½”

2103

1445

1161

993

880

798

734

683

641

605

536

486

416

2”

4050

2784

2235

1913

1696

1536

1413

1315

1234

1165

1033

936

801

Propane Supply Piping

Based on 11” WC supply pressure

Pipe

 

 

 

 

 

kBTU of Propane

 

 

 

 

 

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Length

10’

20’

30’

40’

50’

60’

70’

80’

90’

100’

125’

150’

200’

½”

275

189

152

129

114

103

96

89

83

78

69

63

55

¾”

567

393

315

267

237

217

196

185

173

162

146

132

112

1”

1071

732

590

504

448

409

378

346

322

307

275

252

213

1 ¼”

2205

1496

1212

1039

913

834

771

724

677

630

567

511

440

1 ½”

3307

2299

1858

1559

1417

1275

1181

1086

1023

976

866

787

675

2”

6221

4331

3465

2992

2646

2394

2205

2047

1921

1811

1606

1496

1260