Program Cooling Temperatures

Program Cooling Temperatures

!CAUTION

If outside temperature is below 50°F, we recommend that you remove the thermo- stat from the wall before proceeding with the following steps to program cooling temperatures. Personal injury or prop- erty damage may occur due to air condi- tioner compressor slugging. A fresh 9 volt Energizer® alkaline battery must be installed to perform off-wall program- ming. Programming away from the wall should prevent accidental compressor operation. BE SURE SYSTEM SWITCH IS SET TO OFF POSITION BEFORE RE- ATTACHING THE THERMOSTAT TO THE SUBBASE!

1.To program cooling temperatures for the heating/cooling periods you have already

set, press

SYSTEM

until COOL appears.

SWITCH

2. Press VIEW once. The Monday heating/

PRGM

cooling period 1 start time you just pro- grammed will appear, and the currently pro- grammed cooling temperature (A, B, C, or D) will be displayed.

3.Press Manual background or Manual background to display the COOL A, B, C, or D temperature you want for Monday’s heating/cooling period 1.

4.Press PRGMVIEW , then press Manual background or Manual background to select Monday’s COOL A, B, C, or D tem- perature for period 2.

5.Repeat steps 3 and 4 for Monday’s heating/ cooling periods 3 and 4.