Operation

Battery Charger Voltage Settings

Table 3-5Battery Charger Voltage Settings

Battery Type and

Acceptance Voltage/

 

 

Temperature

Max Time

Float Voltage

Equalize Voltage

 

 

 

 

 

12-volt wet cell

14.0

/ 1 hour

13.1

15.8

warm temperature

 

 

 

 

12-volt wet cell

14.4

/ 1 hour

13.5

16.3

cool temperature

 

 

 

 

12-volt gel cell

13.8

/ 3 hours

13.3

14.1**

warm temperature

 

 

 

 

12-volt gel cell

14.1

/ 3 hours

13.6

14.1**

cool temperature

 

 

 

 

24-volt wet cell

28.0

/ 1 hour

26.2

31.6

warm temperature

 

 

 

 

24-volt wet cell

28.8

/ 1 hour

27.0

32.6

cool temperature

 

 

 

 

24-volt gel cell

27.6

/ 3 hours

26.6

27.6

warm temperature

 

 

 

 

24-volt gel cell

28.2

/ 3 hours

27.2

28.2

cool temperature

 

 

 

 

 

 

 

 

 

** When set for gel cells, the equalize mode is disabled.