INSTALLATION OPTION 4 (Dual AC Input)
Fleet Power 2500 Only
•50 Amp 120 Volt Shore Power Service
•Generator
The transfer switch shown, switches, either manually or automati- cally, between generator and shore power. This switch is unrelated to the transfer switch inside the Fleet Power 2500. This AC panel has a single 120 volt leg.
The transfer AC input and the Charger AC input are fed from separate 30 Amp circuit breakers. Make sure the wiring between the AC panel and the inverter will safely carry two 30 Amp circuits. Typically, a minimum of 10 AWG wires would be used. 6 each (2 hot, 2 neutral and 2 ground).
Please note that the inverter AC output breakers are isolated from the main panel.
Keeping the inverter loads isolated is important. Do not back feed the unit by supply- ing AC from shore or generator to the inverter AC output. Three inverter breakers are shown in the particular diagram. You are not limited to three breakers.
32
10/97 Fltman.pm65