Preventative Maintenance
5–6 152607
Periodic Maintenance
Xantrex Technology recommends that the following prevent ative maintenance
procedures be carried out on the PV225S.

Monthly Intervals or As Required

Perform the following preventative ma intenance tasks on a monthly basis or as
required.

Aluminum Extrusion Heatsinks

Inspect the aluminum extrusion heatsinks and external c ooling fans for
accumulation of dirt and debris. Accumulation of dirt and debr is on the
aluminum extrusion heatsinks and external cooling fa ns will decrease their
ability to transfer heat, which may cause the PV225S to enter a fault state
based upon an over-temperature alarm. Remove a nd clean if debris is present.

Fan Operation

Verify proper operation of the external cooling fans (B1 and B2) located
above the matrix aluminum extrusion heatsinks. These fans operate when the
K1 contactor is closed. If present, remove a ny debris from the fans.

Internal Circulation Fan

Verify the internal circulation fan (B3) is operating whenever there is utili ty
power applied to the PV225S.

Inductor Enclosure Cooling Fans

Verify that the inductor enclosure cooling fans (B4 and B5) operate whenever
the PV225S is processing power. The airflow direction should be from the
outside, forcing air into the enclosure. If prese nt, remove any debris from the
fans.