Auto-restart Feature
152607 2–23

Any State Fault

If the PV225S encounters a fault, regardless o f operating state, it will transition to
the Fault state. The PV225S will remain in this state until the fault condition has
been remedied and cleared. The Fault Code number will appear on the f irst line of
the LCD. A description of the fault will show on the second li ne. The third line of
the LCD will read “
F1 to Clear Fault?
”. The fourth line shows the goal state.
To clear the fault:
1. See Table 4-1, “Fault Codes” on page 4–4 for a complete listing of Fault
Codes and possible remedies. Correct the fault condit ion if possible and
attempt to clear the fault by pressing “F1”.
2. The ability to clear the fault can only be done from the READ Menu. If a fault
occurs while accessing the WRITE Menu, press ing <MENU> once will return
to the Read Menu, and “
F1 to Clear Fault
” will appear on the third line
of the LCD display.
Auto-restart Feature
In the event of a utility voltage or fr equency excursion outside of those specified
in Table A-3 on page A–3, the PV225S will automatically transition to a Faul t
condition. Once the Utility recovers for a per iod of five minutes, the PV225S will
automatically clear the fault, then res ume normal operation.
Figure 2-8
LCD showing Fault Code
LCD Display showing
Fault Code
UFCU Keypad
Fault: 0070
INTERLOCK ACTIVATED
F1 to Clear Fault
Goal: PWR Tracking