Clearing Faults Manually
152607 4–3
Clearing Faults Manually
Faults associated with a grid disturbance clear autom atically. These faults include:
0010 (AC Frequency Low),
0011 (AC Frequency High),
0012 AC Voltage Low), and
0013 (AC Voltage High) only.
Once the AC voltage and frequency return to within the acceptable range, the
PV225S will clear the fault and automatically re start after a 5-minute delay. All
other faults associated with the PV225S must be circumv ented and cleared
manually using the UFCU.The following procedure des cribes how to manually
clear a fault message from the LCD.
To clear the fault:
1. Determine the source of the fault using Table 4-1, “Fault Codes” on page 4–4.
Correct the fault condition.
2. Ensure the fault code and “
Clear Fault?
” message is displayed in the LCD.
a) If the “
Clear Fault?
” message is not shown on the second line of the
LCD, scroll through the read parameter menu with the /\ or \/ keys until
the message appears.
3. To clear the fault, press <ENTER>. The PV225S will transition to Sleeping
mode.
Figure 4-1
LCD showing Fault Code

Important::

If the fault does not clear, the fault condition has not been corrected.
LCD Display showing
Fault Code
UFCU Keypad
0071
PV SWITCH OPEN
F1 to Clear Fault?
Goal: PWR TRACKING