Operation
2–16 152607
Changing and Displaying WRITE Menu Parameter Values
Follow the procedure below to change WRITE Menu paramete rs.
To c han ge WRITE Menu parameters:
1. From the standard display or anywhere i n the READ Menu, you may access
the WRITE menu parameters by pressing the <MENU> key. This will ask for a
password.
2. Enter the password <5><9><4> and press the <ENTER> button.
a) If the wrong password is entered, the display w ill again prompt the user
for the password.
b) If a mistake is made while keying in the password, the /\ or \/ key s may be
used as a backspace key.
3. Once within the Write Menu, the first item is the “Set Goal State”. Use the /\
or \/ key on the operator interface keypa d to scroll through the WRITE Menu
parameters.
a) To change the displayed parameter, press the <ENTER> button.
b) Enter the desired value and press <ENTER>. If the value entered is outside
the acceptable range for the parameter, the original va lue will remain.
c) To leave the WRITE Menu and return to the READ Menu, press the
<MENU> button once and the standard display will reappear on the L CD.
Table 2-5
Write Menu Parameters
Parameter Description ID Units
Default
Valu e
Maximum
Valu e
Minimum
Valu e
Set Goal State
Displays as:
Hit ENTER to set
Goal:
Commands a Goal State.
Set Date
Displays as:
042805
The date is entered
month-day-year (mmddyy):
April 28, 2005 is entered
042805
.
Set Time:
Displays as:
163000
The time is entered in military
hours-minutes-seconds
(i.e., 24-hour clock): 4:30 pm is
entered
163000
.
Maximum Grid
Volt age
Displays as:
Max AC Volts %:
This parameter sets the trigger
point value for “AC voltage High”
(0013) fault. If the grid voltage is
over this parameter’s value, the
fault is triggered. The upper limit
of this parameter is restricted by
UL requirements.
32 Percentage
of
Nominal
voltage
110 110 105