System Status Displays
975-0210-01-01 31
When the initiating condition (battery voltage or thermostat
signal) has occurred, the Pending Genstart message is
displayed for approximately two minutes, awaiting a change in
the condition or a manual override. If neither condition occurs,
the inverter/charger attempts to start the generator and the RC/
GS displays “Cranking Genset.”
Once the generator starts, there is a brief delay to allow the
generator to reach operating speed and for the inverter/
charger to synchronize to the generator, at which point the
screen shows that AC is again available.
Starter Cooldown and Gen Start (RC/GS Only)
If the generator does not start within 60 seconds, a two-
minute starter cooldown message is displayed after which
another attempt to start the generator occurs.1 The RC/GS
will make a total of three start attempts.
1.These are maximum times. They vary according to the Genset you have selected.
Genset Status:
Cranking Genset
Genset Status:
AC Available
Genset Status:
Starter Cooldown
RC-GS_manual.book Page 31 Friday, May 20, 2005 4:57 PM