Installation

Dry

Do not allow water or other liquids to drop or

 

splash on the inverter.

 

 

Cool

Ambient air temperature should be between

 

32 ºF and 104 º F (0 ºC and 40 º C)—the cooler

 

the better within this range.

 

 

Ventilated

Allow at least 2 inches (5 cm) of clearance

 

around the inverter for air flow. Ensure that

 

ventilation openings on the DC end and the

 

bottom of the unit are not obstructed.

 

 

Safe

Do not install the inverter in the same

 

compartment as batteries or in any

 

compartment capable of storing flammable

 

liquids like gasoline.

 

 

Close to battery

Do not use excessive DC cable lengths: they

 

increase wire resistance and reduce input

 

power.

 

 

Protected from

Do not mount the inverter where it will be

battery gases

exposed to gases produced by the batteries.

 

These gases are very corrosive and prolonged

 

exposure will damage the inverter.

 

 

Mount The Inverter

1.Select an appropriate mounting location and orientation. The unit can be oriented in any way, such as:

• Horizontally on a vertical surface or

DC connections should NOT point up or down.

• On or under a horizontal surface.

2.Hold the inverter against the mounting surface and mark the positions using the mounting flanges as guide.

3.Pilot-drill the four mounting holes.

4.Fasten the inverter to the mounting surface using corrosion- resistant hardware sized #10.