Operation

Operating Limits

Power Output

The PROwatt SW Inverter will deliver the following power continuously, depending on input voltage and ambient temperature. The inverter will deliver more than 10% of its continuous power rating for approximately five minutes. The inverter must cool down for 15 minutes before it can resume operation above its continuous power rating.

 

 

Output

Input

Tempera

Model

Powera

Currentb

Voltage

ture

 

 

 

 

 

PROwatt SW 600

540 W

4.5 A

 

Ambient

 

 

 

 

PROwatt SW 1000

900 W

7.5 A

 

13 Vdc

25 °C

 

 

 

 

(77 °F)

PROwatt SW 2000

1800 W

15 A

 

 

 

 

 

 

 

 

a.Applies to resistive loads such as incandescent lights. b.Applies to reactive loads such as motors.

Input Voltage

The input voltage limits are shown in the following table.

Operating

 

 

Condition

Voltage Range

Comment

 

 

 

Normal

10.5–15.5 V

n/a

 

 

 

Peak Performance

13–14.5 V

n/a

 

 

 

Low Voltage Alarm

Voltage is

The audible low battery

 

11.0 V or less

alarm sounds.

 

 

 

Operating

 

 

Condition

Voltage Range

Comment

 

 

 

Low Voltage

Voltage is

The unit shuts down to

Shutdown

10.5 V or less.

protect the battery from

 

 

being over-discharged.

 

 

 

High Voltage

Voltage is

The unit shuts down to

Shutdown

15.5 V or more.

protect itself from

 

 

excessive input voltage.

 

 

Note: Although the

 

 

PROwatt SW Inverter

 

 

incorporates over-

 

 

voltage protection, it can

 

 

still be damaged if input

 

 

voltage exceeds 16 V.

 

 

 

Unit restarts after

11.5 V

The unit will not restart

low voltage

 

unless the battery

shutdown

 

voltage is acceptable for

 

 

running the load.

 

 

 