COMMS SCREEN

Operation

COMMS SCREEN

FIG. 22

00522VIPC

 

OVERVIEW

This screen is accessed from the RCC Setup Screen. This screen allows definition of the necessary com- munications parameters. Refer to PRINTER Section of this book for details of the Printer connections and setup.

DISPLAY ONLY

RS-485 Baud Rate 4800

Shows the baud rate at which the panel shall com- municate through the Com3 port to the remote control panel(s). The baud rate of the remote control panel(s) must be set for 4800 in the EPROM. Make sure the correct EPROM is installed at the chiller/condenser control panel(s). See Table 1.

PROGRAMMABLE

RCC Poll Time (5-30 sec.)

Define the poll time (how frequently) this panel requests for data from another panel through the Com3 port.

NAVIGATION

Home

Causes an instant return to the Home Screen.

Setup

Return to the Setup Screen.