York 292443-XTG-D-0508 manual Typical Field Power Wiring Diagram, Electrical Data

Models: 292443-XTG-D-0508

1 28
Download 28 pages 58.49 Kb
Page 15
Image 15
FIGURE 4 - TYPICAL FIELD POWER WIRING DIAGRAM

292443-XTG-D-0508

CONTACTOR

FIELD-SUPPLIED

DISCONNECT

REFER TO ELECTRICAL

GROUND

DATA TABLES TO SIZE

LUG

THE DISCONNECT

 

 

CONTACTOR

GROUND

LUG REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT

SINGLE

TABLE 12: ELECTRICAL DATA PHASE

Manual background POWER

SUPPLY

FIELD-SUPPLIED

DISCONNECT

THREE

Manual backgroundPHASE

POWER

SUPPLY

FIGURE 4 - TYPICAL FIELD POWER WIRING DIAGRAM

TABLE 12: ELECTRICAL DATA

 

 

VOLTAGE

COMPRESSOR

COND.

SUPPLY

 

MAX.

MAX.

 

 

MODEL

POWER

LIMITATIONS1

AIR

MINIMUM

HACR

UNIT

TRANSFORMER

 

 

FAN

FUSE

DNA

SUPPLY

 

 

 

 

MOTOR,

BLOWER

CIRCUIT

SIZE,

BREAKER

POWER

SIZE (VA)

MIN.

MAX.

RLA

LRA

 

 

FLA

MOTOR

AMPACITY

AMPS2

SIZE,

FACTOR

 

 

 

 

 

 

 

 

FLA

 

 

AMPS

 

 

030

208/230-1-60

187

253

14.7

73

1.1

2.2

21.7

30

30

0.96

40

036

208/230-1-60

187

253

17.3

94

1.1

3.5

26.2

35

35

0.96

40

036

208/230-3-60

187

253

10.9

78

1.1

3.5

18.2

25

25

0.96

75

 

 

 

 

 

 

 

 

 

 

 

 

 

036

460-3-60

414

504

5.8

40

0.6

1.8

9.6

15

15

0.96

75

042

208/230-1-60

187

253

15.4

86

1.1

3.5

23.9

30

30

0.96

40

042

208/230-3-60

187

253

11.5

88

1.1

3.5

19

25

25

0.96

75

 

 

 

 

 

 

 

 

 

 

 

 

 

042

460-3-60

414

504

5.8

42

0.6

1.8

9.7

15

15

0.96

75

048

208/230-1-60

187

253

24.4

140

1.3

7

38.8

50

50

0.96

40

048

208/230-3-60

187

253

14.1

105

1.3

7

25.9

35

35

0.96

75

 

 

 

 

 

 

 

 

 

 

 

 

 

048

460-3-60

414

504

7.1

55

0.7

3.5

13.1

20

20

0.96

75

060

208/230-1-60

187

253

28.9

175

1.3

7

44.4

60

60

0.96

40

060

208/230-3-60

187

253

15.5

125

1.3

7

29.5

40

40

0.96

75

 

 

 

 

 

 

 

 

 

 

 

 

 

060

460-3-60

414

504

8.9

66.5

0.7

3.5

15.4

20

20

0.96

75

1.Utilization range “A” in accordance with ARI Standard 110.

2.Dual element, time delay type.

Johnson Controls Unitary Products

15

Page 15
Image 15