TABLE 8: SIDE SUPPLY AIR BLOWER PERFORMANCE1
|
|
|
|
|
|
|
|
|
|
|
|
| EXTERNAL STAIC PRESSURE - IWG |
|
|
|
|
|
|
|
|
|
|
| ||||||||
MODEL # | MTR | .10 |
| .20 |
| .30 |
| .40 | .50 |
| .60 |
| .70 |
| .80 |
| .90 |
| 1.00 | 1.10 |
| |||||||||||
DNA | SPD | CFM |
| WATTS | CFM |
| WATTS | CFM |
| WATTS | CFM | WATTS | CFM |
| WATTS | CFM |
| WATTS | CFM |
| WATTS | CFM |
| WATTS | CFM |
| WATTS | CFM | WATTS | CFM |
| WATTS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| HI | - |
| - | - |
| - | 1238 |
| 504 | 1165 | 484 | 1075 |
| 463 | 984 |
| 443 | 894 |
| 422 | 751 |
| 390 | - |
| - | - | - | - |
| - |
030 | MED | 994 |
| 333 | 947 |
| 321 | 901 |
| 309 | 854 | 297 | 774 |
| 280 | - |
| - | - |
| - | - |
| - | - |
| - | - | - | - |
| - |
| LOW | - |
| - | - |
| - | - |
| - | - | - | - |
| - | - |
| - | - |
| - | - |
| - | - |
| - | - | - | - |
| - |
| HI | - |
| - | - |
| - | - |
| - | - | - | 1465 |
| 712 | 1390 |
| 685 | 1315 |
| 657 | 1204 |
| 623 | 1093 |
| 588 | 982 | 554 | - |
| - |
036 | MED | 1432 |
| 650 | 1381 |
| 628 | 1330 |
| 605 | 1279 | 583 | 1210 |
| 556 | 1140 |
| 529 | 1071 |
| 502 | 977 |
| 477 | - |
| - | - | - | - |
| - |
| LOW | 1191 |
| 527 | 1149 |
| 510 | 1107 |
| 494 | 1065 | 477 | 1009 |
| 459 | 952 |
| 441 | - |
| - | - |
| - | - |
| - | - | - | - |
| - |
| HI | - |
| - | 1681 |
| 797 | 1610 |
| 768 | 1540 | 740 | 1465 |
| 712 | 1390 |
| 685 | 1315 |
| 657 | 1204 |
| 623 | 1093 |
| 588 | - | - | - |
| - |
042 | MED | 1432 |
| 650 | 1381 |
| 628 | 1330 |
| 605 | 1279 | 583 | 1210 |
| 556 | 1140 |
| 529 | - |
| - | - |
| - | - |
| - | - | - | - |
| - |
| LOW | 1191 |
| 527 | 1149 |
| 510 | 1107 |
| 494 | 1065 | 477 | - |
| - | - |
| - | - |
| - | - |
| - | - |
| - | - | - | - |
| - |
| HI | - |
| - | - |
| - | - |
| - | 1908 | 1023 | 1832 |
| 982 | 1737 |
| 938 | 1656 |
| 889 | 1348 |
| 789 | 1252 |
| 754 | - | - | - |
| - |
048,060 | MED | - |
| - | - |
| - | - |
| - | 1773 | 894 | 1726 |
| 869 | 1674 |
| 852 | 1613 |
| 832 | 1339 |
| 731 | - |
| - | - | - | - |
| - |
| LOW | - |
| - | - |
| - | 1672 |
| 841 | 1610 | 804 | 1542 |
| 773 | - |
| - | - |
| - | - |
| - | - |
| - | - | - | - |
| - |
1.Above data includes allowances for a dry evaporator coil, gas heat exchanger and no filters. For additional pressure drops, refer to Table 10 and 11.
TABLE 9: BOTTOM SUPPLY AIR BLOWER PERFORMANCE1
|
|
|
|
|
|
|
|
| EXTERNAL STATIC PRESSURE - IWG |
|
|
|
|
|
|
|
| |||||||
MODEL # | MTR | .10 |
| .20 |
| .30 |
| .40 | .50 |
| .60 |
| .70 |
| .80 |
| .90 | 1.00 | 1.10 | |||||
CFM | WATTS | CFM | WATTS | CFM | WATTS | CFM | WATTS | CFM | WATTS | CFM |
| WATTS | CFM | WATTS | CFM | WATTS | CFM | WATTS | CFM | WATTS | CFM | WATTS | ||
DNA | SPD |
| ||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| HI | - | - | - | - | 1115 | 454 | 1049 | 436 | 967 | 417 | 886 |
| 398 | 805 | 380 | 676 | 351 | - | - | - | - | - | - |
030 | MED | 895 | 300 | 853 | 289 | 811 | 278 | 769 | 267 | 697 | 252 | - |
| - | - | - | - | - | - | - | - | - | - | - |
| LOW | - | - | - | - | - | - | - | - | - | - | - |
| - | - | - | - | - | - | - | - | - | - | - |
| HI | - | - | - | - | - | - | - | - | 1458 | 688 | 1377 |
| 663 | 1295 | 639 | 1147 | 600 | 999 | 561 | - | - | - | - |
036 | MED | 1482 | 628 | 1428 | 613 | 1374 | 599 | 1320 | 584 | 1242 | 556 | 1163 |
| 528 | 1085 | 500 | 961 | 474 | - | - | - | - | - | - |
| LOW | 1239 | 510 | 1184 | 496 | 1130 | 481 | 1075 | 467 | 998 | 448 | 922 |
| 428 | - | - | - | - | - | - | - | - | - | - |
| HI | - | - | 1687 | 763 | 1614 | 737 | 1540 | 712 | 1458 | 688 | 1377 |
| 663 | 1295 | 639 | 1147 | 600 | - | - | - | - | - | - |
042 | MED | 1482 | 628 | 1428 | 613 | 1374 | 599 | 1320 | 584 | 1242 | 556 | 1163 |
| 528 | 1085 | 500 | - | - | - | - | - | - | - | - |
| LOW | 1239 | 510 | 1184 | 496 | 1130 | 481 | 1075 | 467 | - | - | - |
| - | - | - | - | - | - | - | - | - | - | - |
| HI | - | - | - | - | - | - | 1928 | 1032 | 1844 | 994 | 1636 |
| 923 | 1515 | 888 | 1441 | 849 | - | - | - | - | - | - |
048,060 | MED | - | - | - | - | - | - | 1805 | 837 | 1693 | 859 | 1580 |
| 819 | 1473 | 788 | - | - | - | - | - | - | - | - |
| LOW | - | - | - | - | 1725 | 850 | 1660 | 807 | 1557 | 776 | 1428 |
| 728 | - | - | - | - | - | - | - | - | - | - |
1.Above data includes allowances for a dry evaporator coil, gas heat exchanger and no filters. For additional pressure drops, refer to Tables 10 and 11.
Johnson Controls Unitary Products | 13 |