to shipment. All unit wiring shall be both numbered and color coded. All units shall be manufactured in a facility cer- tified to ISO 9001 standards, and the cooling performance shall be rated in accordance with DOE and ARI test proce- dures. The heating performance shall be rated to DOE and GAMA test procedures. Units shall be CSA listed and classi- fied to ANSI Z21.47/CAN/CSA 2.3 standards and UL 1995/ CAN/CSA No.
UNIT CABINET
Unit cabinet shall be constructed of galvanized steel, with exterior surfaces coated with a
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be direct drive,
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the
rosion resistant steel spider bracket and shall be statically balanced for smooth operation. The outdoor fan motor shall be totally enclosed with permanently lubricated bearings and internally protected against overload conditions.
REFRIGERANT COMPONENTS
Compressors:
a.Shall be fully hermetic type, direct drive, internally protected with internal
b.Shall have internal isolation and sound muffling to minimize vibration and noise, and be externally iso- lated on a dedicated, independent mounting.
Coils:
a.Evaporator and condenser coils shall have alumi- num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed.
b.Evaporator coil shall be of the direct expansion, blow through design, while condenser coil shall be draw through design.
Refrigerant Circuit and Refrigerant Safety Components:
a.Shall include independent
b.Shall include filter/strainer to eliminate any foreign matter.
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125º F out- door temperature, exceeding maximum load criteria ARI Standard 210/240. The compressor, with standard controls, shall be capable of operation down to 45º F outdoor tempera- ture. Accessory low ambient kit shall be available for opera- tion to 0º F.
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.
Johnson Controls Unitary Products | 25 |