TABLE 7: DNA060 COOLING CAPACITIES - 5 TON

TEMPERATURE

 

 

 

 

 

 

 

 

 

AIR ON EVAPORATOR COIL

 

 

 

 

 

 

 

 

 

1,500 CFM

 

 

1,750 CFM

 

 

 

2,000 CFM

 

 

2,250 CFM

 

 

2,500 CFM

 

OF AIR ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB °F

 

 

WB °F

 

 

 

WB °F

 

 

WB °F

 

 

WB °F

 

CONDENSER COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

67

62

57

72

67

62

57

 

72

67

62

57

72

67

62

57

72

67

62

57

 

 

NET CAP.

 

60.3

56.2

52.0

51.1

62.4

58.1

53.8

52.9

 

64.4

60.0

55.5

54.6

65.4

60.9

56.4

55.5

66.5

61.8

57.3

56.3

 

 

 

MBH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TOTAL POWER

5.67

5.58

5.48

5.50

5.80

5.71

5.61

5.63

 

5.93

5.83

5.73

5.75

6.11

6.01

5.91

5.93

6.30

6.20

6.09

6.11

 

 

INPUT kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CapacitySensible

 

 

 

 

86

39.5

47.7

52.0

51.1

43.5

52.3

53.8

52.9

 

47.5

56.9

55.5

54.6

50.9

59.4

56.4

55.5

54.3

61.8

57.3

56.3

85 °F

MBH

 

DryEntering °FBulb

 

83

35.2

43.4

50.6

50.9

38.4

47.2

53.1

52.7

 

41.6

51.0

55.5

54.6

44.3

54.1

56.4

55.5

46.9

57.2

57.3

56.3

 

 

1

 

 

 

80

31.0

39.1

46.4

46.6

33.4

42.2

50.0

50.2

 

35.8

45.2

53.6

53.9

37.6

47.5

55.4

55.1

39.4

49.8

57.3

56.3

 

 

 

 

 

 

77

26.7

34.8

42.1

42.3

28.3

37.1

44.9

45.2

 

30.0

39.4

47.8

48.1

31.0

40.9

48.8

48.5

32.0

42.3

49.8

48.9

 

 

 

 

 

 

74

22.4

30.5

37.8

38.0

23.3

32.0

39.9

40.1

 

24.2

33.6

42.0

42.2

24.3

34.2

42.2

41.8

24.5

34.9

42.4

41.4

 

 

 

 

 

 

71

-

26.3

33.5

33.8

-

27.0

34.8

35.1

 

-

27.7

36.1

36.4

-

27.6

35.5

35.2

17.1

27.4

34.9

34.0

 

 

 

 

 

 

68

-

22.0

29.3

29.5

-

21.9

29.8

30.0

 

-

21.9

30.3

30.6

-

20.9

28.9

28.5

9.6

20.0

27.5

26.5

 

 

NET

CAP.

 

 

57.6

53.0

49.0

48.5

59.5

54.7

50.7

50.1

 

61.5

56.5

52.3

51.7

62.4

57.3

53.1

52.4

63.3

58.1

53.9

53.2

 

 

 

MBH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TOTAL POWER

6.14

6.11

5.96

6.01

6.30

6.27

6.11

6.16

 

6.45

6.42

6.26

6.32

6.62

6.59

6.43

6.49

6.80

6.76

6.60

6.65

 

 

INPUT kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CapacitySensible

 

 

 

 

86

37.6

46.8

49.0

48.5

41.5

51.4

50.7

50.1

 

45.3

56.0

52.3

51.7

48.6

57.1

53.1

52.4

51.8

58.1

53.9

53.2

95 °F

MBH

 

DryEntering °FBulb

 

83

33.3

42.5

48.6

48.2

36.4

46.4

50.5

50.0

 

39.5

50.2

52.3

51.7

41.9

53.1

53.1

52.4

44.4

56.1

53.9

53.2

 

 

1

 

 

 

80

29.1

38.3

44.4

43.9

31.4

41.3

47.9

47.4

 

33.7

44.3

51.4

50.9

35.3

46.5

52.6

52.1

36.9

48.6

53.9

53.2

 

 

 

 

 

 

77

24.8

34.0

40.1

39.7

26.3

36.2

42.8

42.4

 

27.8

38.5

45.5

45.1

28.7

39.8

46.0

45.4

29.5

41.2

46.4

45.7

 

 

 

 

 

 

74

20.5

29.7

35.8

35.4

21.3

31.2

37.8

37.3

 

22.0

32.7

39.7

39.2

22.0

33.2

39.3

38.8

22.0

33.7

38.9

38.3

 

 

 

 

 

 

71

-

25.4

31.5

31.1

-

26.1

32.7

32.3

 

-

26.8

33.9

33.4

-

26.6

32.7

32.1

-

26.3

31.5

30.8

 

 

 

 

 

 

68

-

21.2

27.2

26.8

-

21.1

27.6

27.2

 

-

21.0

28.0

27.6

-

19.9

26.0

25.5

-

18.8

24.0

23.4

 

 

NET

CAP.

 

 

53.0

48.8

45.0

42.7

55.0

50.7

46.8

44.3

 

57.1

52.5

48.5

45.9

57.6

53.1

49.0

46.4

58.2

53.6

49.5

46.9

 

 

 

MBH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TOTAL POWER

6.85

6.74

6.64

6.64

6.99

6.88

6.78

6.78

 

7.14

7.03

6.93

6.92

7.34

7.22

7.12

7.12

7.54

7.42

7.31

7.31

 

 

INPUT kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CapacitySensible

 

 

 

 

86

36.1

45.1

45.0

42.7

39.9

48.7

46.8

44.3

 

43.7

52.3

48.5

45.9

46.9

53.0

49.0

46.4

50.1

53.6

49.5

46.9

105 °F

MBH

 

DryEntering °FBulb

 

83

31.8

40.8

44.8

42.6

34.9

44.6

46.7

44.2

 

37.9

48.4

48.5

45.9

40.3

50.5

49.0

46.4

42.6

52.6

49.5

46.9

 

 

1

 

 

 

80

27.6

36.5

41.5

39.4

29.8

39.5

44.9

42.6

 

32.1

42.5

48.3

45.8

33.6

44.6

48.9

46.3

35.2

46.6

49.5

46.9

 

 

 

 

 

 

77

23.3

32.2

37.2

35.1

24.8

34.5

39.8

37.5

 

26.3

36.7

42.4

40.0

27.0

37.9

42.2

39.7

27.7

39.2

42.0

39.4

 

 

 

 

 

 

74

19.0

28.0

32.9

30.8

19.7

29.4

34.8

32.5

 

20.4

30.9

36.6

34.2

20.3

31.3

35.6

33.1

20.3

31.7

34.6

32.0

 

 

 

 

 

 

71

-

23.7

28.6

26.5

-

24.4

29.7

27.4

 

-

25.0

30.8

28.3

-

24.6

29.0

26.4

-

24.2

27.1

24.5

 

 

 

 

 

 

68

-

19.4

24.4

22.3

-

19.3

24.6

22.4

 

-

19.2

24.9

22.5

-

18.0

22.3

19.8

-

16.8

19.7

17.1

 

 

NET

CAP.

 

 

48.4

44.7

41.0

36.9

50.5

46.6

42.8

38.5

 

52.6

48.6

44.6

40.1

52.9

48.8

44.9

40.3

53.2

49.1

45.1

40.5

 

 

 

MBH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TOTAL POWER

7.56

7.37

7.33

7.27

7.69

7.50

7.46

7.40

 

7.82

7.63

7.59

7.53

8.05

7.85

7.81

7.75

8.28

8.08

8.03

7.97

 

 

INPUT kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CapacitySensible

 

 

 

 

86

34.6

43.3

41.0

36.9

38.4

45.9

42.8

38.5

 

42.2

48.6

44.6

40.1

45.2

48.8

44.9

40.3

48.3

49.1

45.1

40.5

115 °F

MBH

 

DryEntering °FBulb

 

83

30.3

39.1

41.0

36.9

33.3

42.8

42.8

38.5

 

36.3

46.5

44.6

40.1

38.6

47.8

44.9

40.3

40.8

49.1

45.1

40.5

 

 

1

 

 

 

80

26.1

34.8

38.6

34.8

28.3

37.7

41.9

37.8

 

30.5

40.7

45.2

40.7

31.9

42.6

45.1

40.6

33.4

44.6

45.1

40.5

 

 

 

 

 

 

77

21.8

30.5

34.3

30.5

23.2

32.7

36.8

32.7

 

24.7

34.9

39.3

34.9

25.3

36.0

38.5

34.0

25.9

37.1

37.7

33.1

 

 

 

 

 

 

74

17.5

26.2

30.0

26.3

18.2

27.6

31.8

27.7

 

18.8

29.0

33.5

29.1

18.7

29.4

31.9

27.4

18.5

29.7

30.2

25.6

 

 

 

 

 

 

71

-

22.0

25.8

22.0

-

22.6

26.7

22.6

 

-

23.2

27.7

23.2

-

22.7

25.2

20.7

-

22.2

22.8

18.2

 

 

 

 

 

 

68

-

17.7

21.5

17.7

-

17.5

21.7

17.6

 

-

17.4

21.8

17.4

-

16.1

18.6

14.1

-

14.8

15.3

10.7

 

 

NET

CAP.

 

 

43.8

40.5

37.1

31.1

46.0

42.6

38.9

32.7

 

48.2

44.6

40.7

34.3

48.2

44.6

40.8

34.2

48.2

44.6

40.8

34.2

 

 

 

MBH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TOTAL POWER

8.30

8.00

8.00

7.90

8.40

8.10

8.10

8.00

 

8.50

8.20

8.20

8.10

8.80

8.50

8.50

8.40

9.00

8.70

8.70

8.60

 

 

INPUT kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CapacitySensible

 

 

 

 

86

33.1

41.6

37.1

31.1

36.8

43.2

38.9

32.7

 

40.6

44.8

40.7

34.3

43.5

44.7

40.8

34.2

46.5

44.6

40.8

34.2

125 °F

MBH

 

DryEntering °FBulb

 

83

28.8

37.3

37.3

31.2

31.8

41.0

39.0

32.7

 

34.7

44.7

40.7

34.3

36.9

45.2

40.8

34.2

39.1

45.6

40.8

34.2

 

 

1

 

 

 

80

24.5

33.0

35.7

30.2

26.7

36.0

38.9

32.9

 

28.9

38.9

42.0

35.6

30.3

40.7

41.4

34.9

31.6

42.5

40.8

34.2

 

 

 

 

 

 

77

20.3

28.8

31.4

26.0

21.7

30.9

33.8

27.9

 

23.1

33.1

36.2

29.8

23.6

34.1

34.8

28.3

24.2

35.1

33.3

26.8

 

 

 

 

 

 

74

16.0

24.5

27.1

21.7

16.6

25.9

28.8

22.8

 

17.2

27.2

30.4

24.0

17.0

27.4

28.1

21.6

16.7

27.6

25.9

19.3

 

 

 

 

 

 

71

-

20.2

22.9

17.4

-

20.8

23.7

17.8

 

-

21.4

24.6

18.2

-

20.8

21.5

15.0

-

20.2

18.4

11.9

 

 

 

 

 

 

68

-

15.9

18.6

13.1

-

15.8

18.7

12.7

 

-

15.6

18.7

12.3

-

14.2

14.8

8.2

-

12.7

10.9

4.4

1. These capacities are net capacities (the indoor fan heat is deducted). TABLE 7: DNA060 COOLING CAPACITIES - 5 TON ALL SENSIBLE CAPACITY

12

Johnson Controls Unitary Products

Page 12
Image 12
York 292443-XTG-D-0508 manual DNA060 COOLING CAPACITIES - 5 TON, Johnson Controls Unitary Products

FAQ

What are the cooling capacities of the York Air Conditioner model 292443-XTG-D-0508?

The cooling capacities for different temperatures and air flow rates are provided in the manual.

Is the indoor fan heat deducted from the net capacities in the manual?

Yes, the net capacities provided in the manual have the indoor fan heat deducted.

Who is the manufacturer of the York Air Conditioner model 292443-XTG-D-0508?

The unit is manufactured by Johnson Controls Unitary Products.