TABLE 14 - SUPERHEAT CHARGING TABLE FOR MODEL D1NA042

 

 

 

 

 

 

 

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM/TON

 

 

 

 

TEMPERATURE

 

 

 

 

INDOOR WB TEMPERATURE (F)

 

 

 

 

 

 

(F)

55

57

59

61

63

65

67

69

71

73

 

75

 

 

 

 

65

18.0

19.7

21.4

23.0

24.7

26.3

28.0

29.1

30.2

31.3

 

32.4

 

70

13.4

15.3

17.3

19.3

21.2

23.2

25.2

26.6

28.1

29.6

 

31.1

 

75

8.7

10.9

13.2

15.5

17.8

20.0

22.3

24.2

26.1

28.0

 

29.9

 

80

-

6.6

9.1

11.7

14.3

16.9

19.5

21.7

24.0

26.3

 

28.6

 

85

-

-

5.1

7.9

10.8

13.7

16.6

19.3

21.9

24.6

 

27.3

 

90

-

-

-

6.7

9.3

11.9

14.6

17.4

20.2

23.1

 

25.9

 

95

-

-

-

5.5

7.8

10.2

12.5

15.5

18.5

21.5

 

24.5

 

100

-

-

-

-

6.3

8.0

9.8

12.9

16.1

19.2

 

22.4

 

105

-

-

-

-

-

5.9

7.1

10.3

13.7

16.9

 

20.3

 

110

-

-

-

-

-

-

-

7.8

11.2

14.7

 

18.1

 

115

-

-

-

-

-

-

-

5.2

8.8

12.4

 

16.0

 

TABLE 15 - SUPERHEAT CHARGING TABLE FOR MODEL D1NA048

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM/TON

 

 

 

 

TEMPERATURE

 

 

 

 

INDOOR WB TEMPERATURE (F)

 

 

 

 

 

 

(F)

55

57

59

61

63

65

67

69

71

73

 

75

 

 

 

 

65

20.9

21.8

22.7

23.6

24.4

25.3

26.2

27.4

28.6

29.8

 

31.0

 

70

17.6

18.7

19.7

20.7

21.7

22.7

23.7

25.2

26.6

28.1

 

29.6

 

75

14.4

15.5

16.6

17.8

18.9

20.0

21.2

22.9

24.7

26.4

 

28.2

 

80

11.1

12.4

13.6

14.9

16.1

17.4

18.6

20.7

22.7

24.8

 

26.8

 

85

7.8

9.2

10.6

12.0

13.3

14.7

16.1

18.4

20.8

23.1

 

25.4

 

90

5.8

7.0

8.2

9.3

10.5

11.7

12.9

15.7

18.6

21.5

 

24.4

 

95

-

-

5.8

6.7

7.7

8.6

9.6

13.0

16.5

19.9

 

23.3

 

100

-

-

5.4

6.0

6.7

7.4

8.0

11.6

15.2

18.7

 

22.3

 

105

-

-

-

5.3

5.7

6.1

6.5

10.2

13.9

17.6

 

21.3

 

110

-

-

-

-

-

-

-

8.7

12.6

16.4

 

20.3

 

115

-

-

-

-

-

-

-

7.3

11.3

15.3

 

19.3

 

TABLE 16 - SUPERHEAT CHARGING TABLE FOR MODEL D2NA060

 

 

 

 

 

 

 

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM/TON

 

 

 

 

TEMPERATURE

 

 

 

 

INDOOR WB TEMPERATURE (F)

 

 

 

 

 

 

(F)

55

57

59

61

63

65

67

69

71

73

 

75

 

 

 

 

65

7.0

9.2

11.4

13.6

15.9

18.1

20.3

21.8

23.2

24.7

 

26.1

 

70

6.1

8.4

10.7

13.0

15.2

17.5

19.8

21.2

22.7

24.1

 

25.6

 

75

5.3

7.6

9.9

12.3

14.6

16.9

19.3

20.7

22.2

23.6

 

25.0

 

80

-

6.8

9.2

11.6

14.0

16.3

18.7

20.2

21.6

23.1

 

24.5

 

85

-

6.0

8.4

10.9

13.3

15.8

18.2

19.6

21.1

22.5

 

23.9

 

90

-

-

6.5

8.7

10.8

12.9

15.1

17.1

19.1

21.1

 

23.1

 

95

-

-

-

6.5

8.3

10.1

11.9

14.5

17.1

19.7

 

22.3

 

100

-

-

-

5.9

7.3

8.6

10.0

12.9

15.8

18.7

 

21.6

 

105

-

-

-

5.3

6.2

7.1

8.0

11.3

14.5

17.7

 

20.9

 

110

-

-

-

-

5.2

5.6

6.1

9.6

13.2

16.7

 

20.2

 

115

-

-

-

-

-

-

-

8.0

11.8

15.7

 

19.6

 

Unitary Products Group

15

Page 15
Image 15
York D1NA018, D2NA060 installation instructions 035-18265-001-A-0202