TABLE 5: DH 210 COOLING CAPACITIES (17.5 TON) (CONTINUED)
AIR ON |
|
|
|
|
|
| TEMPERATURE OF AIR ON CONDENSER COIL |
|
|
|
|
| |||||||
|
|
|
| 115°F |
|
|
|
|
|
|
|
| 125°F |
|
|
|
| ||
EVAPORATOR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
COIL |
| TOTAL | POWER |
| SENSIBLE CAPACITY, MBH |
| TOTAL | POWER |
| SENSIBLE CAPACITY, MBH |
| ||||||||
|
| ENTERING DRY BULB, °F |
|
| ENTERING DRY BULB, °F |
| |||||||||||||
|
|
| CAP.1 | INPUT2 |
|
| CAP.1 | INPUT2 |
|
| |||||||||
CFM |
| WB | MBH | KW | 90 | 85 | 80 |
| 75 | 70 | 65 | MBH | KW | 90 | 85 | 80 | 75 | 70 | 65 |
| °F |
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| 77 | 217.8 | 12.5 | 112.3 | 87.3 | 62.4 |
| - | - | - | 207.3 | 10.1 | 108.4 | 83.5 | 58.5 | - | - | - |
|
| 72 | 199.9 | 12.2 | 143.0 | 118.0 | 93.1 |
| 68.1 | - | - | 189.9 | 9.9 | 138.0 | 113.1 | 88.1 | 63.2 | - | - |
5250 |
| 67 | 182.0 | 12.0 | 173.7 | 148.7 | 123.8 |
| 98.9 | 73.9 | - | 172.5 | 9.7 | 167.6 | 142.6 | 117.7 | 92.8 | 67.8 | - |
|
| 62 | 169.7 | 11.8 | 169.7 | 169.7 | 146.7 |
| 121.7 | 96.8 | 71.8 | 163.2 | 9.5 | 163.2 | 163.2 | 140.6 | 115.6 | 90.7 | 65.7 |
|
| 57 | 170.9 | 11.8 | 170.9 | 170.9 | 146.0 |
| 121.1 | 96.1 | 71.2 | 165.4 | 9.6 | 165.4 | 165.4 | 138.8 | 113.8 | 88.9 | 63.9 |
|
| 77 | 223.9 | 16.9 | 142.1 | 98.9 | 69.4 |
| - | - | - | 212.0 | 16.5 | 141.0 | 95.0 | 65.5 | - | - | - |
|
| 72 | 205.5 | 16.5 | 162.5 | 133.0 | 103.5 |
| 74.1 | - | - | 194.2 | 16.2 | 157.5 | 128.0 | 98.5 | 69.1 | - | - |
6125 |
| 67 | 187.1 | 16.1 | 182.9 | 167.2 | 137.7 |
| 108.2 | 78.7 | - | 176.5 | 15.8 | 174.0 | 161.1 | 131.6 | 102.1 | 72.6 | - |
|
| 62 | 174.4 | 15.8 | 174.4 | 174.4 | 163.1 |
| 133.6 | 104.2 | 74.7 | 167.0 | 15.6 | 167.0 | 167.0 | 157.2 | 127.7 | 98.2 | 68.7 |
|
| 57 | 175.7 | 15.8 | 175.7 | 175.7 | 162.4 |
| 132.9 | 103.4 | 74.0 | 169.2 | 15.7 | 169.2 | 169.2 | 155.2 | 125.7 | 96.2 | 66.7 |
|
| 77 | 229.9 | 21.2 | 172.0 | 110.4 | 76.4 |
| - | - | - | 216.8 | 23.0 | 173.6 | 106.4 | 72.4 | - | - | - |
|
| 72 | 211.0 | 20.7 | 182.0 | 148.0 | 114.0 |
| 80.0 | - | - | 198.6 | 22.5 | 177.0 | 143.0 | 109.0 | 74.9 | - | - |
7000 |
| 67 | 192.1 | 20.2 | 192.1 | 185.6 | 151.6 |
| 117.6 | 83.6 | - | 180.4 | 22.0 | 180.4 | 179.5 | 145.5 | 111.5 | 77.5 | - |
|
| 62 | 179.1 | 19.9 | 179.1 | 179.1 | 179.6 |
| 145.6 | 111.6 | 77.5 | 170.8 | 21.6 | 170.8 | 170.8 | 170.8 | 139.7 | 105.7 | 71.7 |
|
| 57 | 180.4 | 19.9 | 180.4 | 180.4 | 178.8 |
| 144.8 | 110.8 | 76.7 | 173.1 | 21.7 | 173.1 | 173.1 | 171.6 | 137.5 | 103.5 | 69.5 |
|
| 72 | 215.7 | 20.8 | 200.1 | 161.4 | 122.6 |
| 83.9 | - | - | 203.1 | 22.6 | 195.0 | 156.3 | 117.5 | 78.8 | - | - |
7875 |
| 67 | 196.4 | 20.3 | 196.4 | 193.2 | 163.1 |
| 124.4 | 85.6 | - | 184.5 | 22.1 | 184.5 | 184.1 | 156.9 | 118.2 | 79.4 | - |
| 62 | 183.1 | 20.0 | 183.1 | 183.1 | 183.4 |
| 144.6 | 105.9 | 67.1 | 174.7 | 21.7 | 174.7 | 174.7 | 174.7 | 137.4 | 98.7 | 59.9 | |
|
|
| |||||||||||||||||
|
| 57 | 184.4 | 20.0 | 184.4 | 184.4 | 183.6 |
| 144.9 | 106.1 | 67.4 | 177.0 | 21.8 | 177.0 | 177.0 | 176.3 | 137.5 | 98.8 | 60.0 |
|
| 72 | 220.4 | 20.9 | 218.2 | 174.8 | 131.3 |
| 87.8 | - | - | 207.7 | 22.7 | 207.7 | 169.5 | 126.1 | 82.6 | - | - |
8750 |
| 67 | 200.7 | 20.4 | 200.7 | 200.7 | 174.6 |
| 131.1 | 87.7 | - | 188.7 | 22.2 | 188.7 | 188.7 | 168.4 | 124.9 | 81.4 | - |
| 62 | 187.1 | 20.1 | 187.1 | 187.1 | 187.1 |
| 143.6 | 100.2 | 56.7 | 178.6 | 21.8 | 178.6 | 178.6 | 178.6 | 135.1 | 91.6 | 48.1 | |
|
|
| |||||||||||||||||
|
| 57 | 188.5 | 20.1 | 188.5 | 188.5 | 188.5 |
| 145.0 | 101.5 | 58.1 | 181.0 | 21.9 | 181.0 | 181.0 | 181.0 | 137.5 | 94.0 | 50.5 |
1.These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Performance Table for the KW of the supply air blower motor.
2.These ratings include the condenser fan motors (Total 1 KW) and the compressor motors but not the supply air blower motor.
Nominal Rating
Johnson Controls Unitary Products | 13 |