York DH 240, DH 210 Blower Motor And Drive Data, STATIC RESISTANCES1, Power Exhaust Performance

Models: DH 240 DH 300 DH 180 DH 210

1 44
Download 44 pages 54.92 Kb
Page 27
Image 27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

262260-YTG-E-1008

TABLE 16: BLOWER MOTOR AND DRIVE DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOTOR1

ADJUSTABLE MOTOR PULLEY

FIXED BLOWER PULLEY

 

BELT

 

MODEL

 

BLOWER

 

(NOTCHED)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRIVE

RANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EFF.

DESIG-

OUTSIDE

PITCH

BORE

DESIG-

OUTSIDE

PITCH

BORE

DESIG-

PITCH

 

SIZE

 

(RPM)

 

 

 

 

 

HP

FRAME

(%)

NATION

DIA.

DIA.

(IN.)

NATION

DIA.

DIA.

(IN.)

NATION

LENGTH

QTY.

 

 

 

 

 

 

 

 

 

 

(IN.)

(IN.)

 

 

(IN.)

(IN.)

 

 

(IN.)

 

 

Standard

850/1065

 

 

 

 

 

4.3-5.32

 

BK90

8.75

8.4

1

BX70

82.8

1

15 TON

 

 

5

184 T

83

1VP56

5.35

1-1/8

 

 

 

 

 

 

 

High

965/1190

BK80

7.75

7.4

1

BX68

69.8

1

 

Static

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17.5 &

Standard

870/1025

 

 

 

 

 

5.5-6.52

 

BK120

11.75

11.4

1-3/16

BX83

84.8

1

High

 

7.5

213 T

89

1VP68

6.75

1-3/8

 

 

 

 

 

 

 

20 TON

950/1120

BK110

10.75

10.4

1-3/16

BX81

82.8

1

Static

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

950/1120

10

215 T

89.5

1VP68

6.75

5.5-6.52

1-3/8

1B5V110

11.3

11.1

1-7/16

BX81

82.8

1

25 TON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

1140/1365

15

254 T

91

1VP75X

7.5

6.2-7.4

1-5/8

1B5V94

9.7

9.5

1-7/16

5VX840

84.0

1

 

Static

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because they are located in the moving air, upstream of any heating device.

2.Do NOT close this pulley below 1 turn open.

TABLE 17: STATIC RESISTANCES1

 

 

 

 

 

 

 

 

RESISTANCE, IWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15 TON

 

 

17.5 TON

 

 

20 TON

 

 

25 TON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4500

6000

7200

6000

 

8000

 

9000

 

6000

7000

9400

7500

10000

12500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WET COIL

 

0.1

0.1

0.1

0.1

 

0.1

 

0.1

 

0.1

0.1

0.1

0.1

0.1

0.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18kW

0.3

0.4

0.4

0.4

 

0.4

 

0.5

 

0.4

0.4

0.5

0.4

0.6

0.6

ELECTRIC HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36kW

0.3

0.4

0.5

0.4

 

0.5

 

0.5

 

0.4

0.5

0.5

0.5

0.5

0.6

OPTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54kW

0.4

0.5

0.5

0.5

 

0.5

 

0.6

 

0.5

0.5

0.6

0.5

0.6

0.7

(DH models only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72kW

0.4

0.5

0.5

0.5

 

0.5

 

0.6

 

0.5

0.5

0.6

0.5

0.6

0.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECONOMIZER OPTION

 

0.1

0.1

0.1

0.1

 

0.1

 

0.2

 

0.1

0.1

0.2

0.1

0.2

0.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HORIZONTAL DUCT CONNECTIONS2

0.1

0.2

0.3

0.2

 

0.3

 

0.5

 

0.2

0.3

0.5

0.3

0.5

0.6

1.Deduct theses resistance values from the available unit ESP values listed in the respective blower performance table except for Horizontal Duct Connections.

2.Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures to the ESP values on the respective unit’s blower performance table.

TABLE 18: POWER EXHAUST PERFORMANCE

MOTOR

 

 

 

STATIC RESISTANCE OF RETRUN DUCTWORK, IWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPEED1

 

0.2

0.3

 

 

0.4

 

0.5

 

0.6

CFM

 

kW

CFM

kW

CFM

 

kW

CFM

 

kW

CFM

 

kW

 

 

 

 

 

HIGH2

5250

 

0.83

4500

0.85

4200

 

0.88

3750

 

0.93

3000

 

0.99

MEDIUM

4900

 

0.77

3900

0.79

3500

 

0.82

2900

 

0.85

-

 

-

LOW

4400

 

0.72

3700

0.74

3000

 

0.78

-

 

-

-

 

-

1.Power exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.

2.The factory setting.

Johnson Controls Unitary Products

27

Page 27
Image 27
York DH 240, DH 210, DH 180, DH 300 warranty Blower Motor And Drive Data, STATIC RESISTANCES1, Power Exhaust Performance