TABLE 7: DH 300 COOLING CAPACITIES (25 TON) (CONTINUED)

AIR ON

 

TEMPERATURE OF AIR ON CONDENSER COIL

 

 

 

 

115°F

 

 

 

 

EVAPORATOR

 

 

 

 

 

 

 

COIL

 

TOTAL

POWER

 

SENSIBLE CAPACITY, MBH

 

 

 

ENTERING DRY BULB, °F

 

 

 

 

CAP.1

INPUT2

 

 

CFM

 

WB

MBH

KW

90

85

80

75

70

65

 

°F

 

 

 

 

 

 

 

 

 

 

 

 

77

302.0

29.3

147.5

111.8

76.2

-

-

-

 

 

72

274.5

28.5

198.2

162.6

126.9

91.3

-

-

7500

 

67

247.1

27.7

247.1

213.3

177.7

142.0

106.4

-

 

 

62

242.9

27.1

242.9

242.9

220.0

184.3

148.7

113.1

 

 

57

238.3

27.2

238.3

238.3

208.0

172.3

136.7

101.1

 

 

77

306.2

29.3

187.3

123.2

81.1

-

-

-

 

 

72

278.4

28.5

219.4

177.3

135.1

93.0

-

-

8750

 

67

250.5

27.8

250.5

231.3

189.2

147.0

104.9

-

 

 

62

246.3

27.1

246.3

246.3

234.2

192.1

150.0

107.8

 

 

57

241.6

27.3

241.6

241.6

221.4

179.3

137.2

95.1

 

 

77

310.4

29.4

227.1

134.6

86.0

-

-

-

 

 

72

282.2

28.6

240.5

191.9

143.3

94.7

-

-

10000

 

67

254.0

27.8

254.0

249.2

200.6

152.0

103.4

-

 

 

62

249.7

27.2

249.7

249.7

248.4

199.8

151.2

102.6

 

 

57

244.9

27.3

244.9

244.9

234.9

186.3

137.7

89.1

 

 

72

286.0

28.9

256.9

201.6

146.2

90.9

-

-

11250

 

67

257.4

28.1

257.4

255.1

204.7

149.3

94.0

-

 

62

253.1

27.4

253.1

253.1

252.4

197.1

141.7

86.4

 

 

 

 

57

248.2

27.6

248.2

248.2

239.6

184.2

128.9

73.5

 

 

72

289.8

29.1

273.3

211.2

149.1

87.0

-

-

12500

 

67

260.9

28.3

260.9

260.9

208.7

146.6

84.5

-

 

62

256.4

27.7

256.4

256.4

256.4

194.3

132.2

70.1

 

 

 

 

57

251.5

27.8

251.5

251.5

244.3

182.2

120.1

58.0

1.These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor- mance Table for the KW of the supply air blower motor.

2.These ratings include the condenser fan motors (Total 2.1 KW) and the compressor motors but not the supply air blower motor. Manual background Nominal Rating