COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. | H2RC030S06 |
|
|
|
|
|
|
| |||
INDOOR COIL MODEL NO. |
| G1FA036S17,21 |
|
|
|
|
|
|
| ||
CONDENSING | IDCFM |
| 800 |
|
| 1000 |
|
| 1200 |
| |
ENTERING AIR | ID DB (°F) | 85 | 80 | 75 | 85 | 80 | 75 | 85 | 80 | 75 | |
TEMPERATURE |
|
|
|
|
|
|
|
|
|
| |
ID WB (°F) | 72 | 67 | 63 | 72 | 67 | 63 | 72 | 67 | 63 | ||
| |||||||||||
| T.C. | 31.9 | 30.6 | 28.9 | 27.4 | 30.9 | 29.4 | 23.0 | 31.2 | 29.9 | |
75 |
|
|
|
|
|
|
|
|
|
| |
S.C. | 18.9 | 19.1 | 18.9 | 19.7 | 20.1 | 20.3 | 20.5 | 21.2 | 21.8 | ||
| KW | 1.97 | 1.95 | 1.94 | 1.98 | 1.96 | 1.95 | 1.98 | 1.97 | 1.95 | |
| T.C. | 31.4 | 29.3 | 27.0 | 28.2 | 30.1 | 28.9 | 25.0 | 30.6 | 30.9 | |
85 |
|
|
|
|
|
|
|
|
|
| |
S.C. | 19.2 | 18.9 | 18.1 | 20.1 | 20.7 | 20.2 | 21.1 | 22.0 | 22.4 | ||
| KW | 2.16 | 2.13 | 2.09 | 2.15 | 2.15 | 2.13 | 2.14 | 2.16 | 2.16 | |
| T.C. | 30.9 | 28.1 | 25.0 | 29.0 | 29.2 | 28.4 | 27.1 | 30.1 | 31.9 | |
95 |
|
|
|
|
|
|
|
|
|
| |
S.C. | 19.5 | 18.7 | 17.3 | 20.6 | 20.7 | 20.1 | 21.6 | 22.8 | 22.9 | ||
| KW | 2.35 | 2.30 | 2.24 | 2.32 | 2.34 | 2.31 | 2.29 | 2.34 | 2.37 | |
| T.C. | 28.6 | 25.5 | 22.3 | 28.2 | 26.8 | 24.6 | 27.9 | 27.8 | 26.8 | |
105 |
|
|
|
|
|
|
|
|
|
| |
S.C. | 18.7 | 17.7 | 16.2 | 20.4 | 20.1 | 18.7 | 22.2 | 22.1 | 21.2 | ||
| KW | 2.53 | 2.45 | 2.40 | 2.53 | 2.49 | 2.44 | 2.53 | 2.51 | 2.48 | |
| T.C. | 26.3 | 23.0 | 19.7 | 27.5 | 24.2 | 20.7 | 28.6 | 25.5 | 21.8 | |
115 |
|
|
|
|
|
|
|
|
|
| |
S.C. | 17.9 | 16.7 | 15.2 | 20.3 | 19.0 | 17.3 | 22.8 | 21.3 | 19.5 | ||
| KW | 2.70 | 2.61 | 2.55 | 2.74 | 2.64 | 2.57 | 2.77 | 2.68 | 2.59 | |
| T.C. | 24.0 | 20.4 | 17.0 | 26.7 | 21.7 | 16.8 | 29.4 | 23.2 | 16.7 | |
125 |
|
|
|
|
|
|
|
|
|
| |
S.C. | 17.1 | 15.6 | 14.1 | 20.2 | 17.9 | 16.0 | 23.3 | 20.5 | 17.8 | ||
| KW | 2.88 | 2.76 | 2.70 | 2.94 | 2.79 | 2.70 | 3.00 | 2.84 | 2.69 |
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between
Air Handler | Coil | T.C. | S.C. | KW |
F2RP/F2FP030 |
| 1.01 | 1.08 | 0.99 |
F2RP/F2FP036 |
| 1.03 | 1.10 | 1.01 |
F2RC/F2FC030 |
| 0.99 | 1.01 | 0.99 |
F2RC/F2FC036 |
| 1.03 | 1.05 | 1.01 |
N1AHB1206 | G2FD030(S,H)17 | 1.00 | 1.00 | 1.00 |
N1AHB1206 | G2FD036(S,H)17 | 1.02 | 1.03 | 1.00 |
N1VSB12 | G2FD036(S,H)17 | 1.03 | 1.12 | 0.94 |
N1VSB12 | G2FD046(S,H)17 | 1.07 | 1.15 | 0.95 |
| G1FA030S14 | 0.97 | 0.98 | 0.99 |
| G1FA036S14 | 1.01 | 1.02 | 1.00 |
| G1FA048S17 | 1.04 | 1.05 | 1.00 |
| G1FA048S21 | 1.04 | 0.99 | 1.01 |
| G1HD036 | 1.03 | 1.03 | 1.00 |
| G1NA036S17L | 1.05 | 1.05 | 1.01 |
| G1NA030S17K | 1.01 | 1.01 | 1.00 |
| G1NA030S21M | 1.01 | 1.01 | 1.00 |
| G1UA030S14 | 0.97 | 0.98 | 0.99 |
| G1UA036S14 | 1.01 | 1.02 | 1.00 |
| G1UA036S17,21 | 1.00 | 1.00 | 1.00 |
| G1UA048S17 | 1.04 | 1.05 | 1.00 |
| G1UA048S21 | 1.04 | 0.99 | 1.01 |
| G2FD030(S,H)17 | 1.00 | 1.00 | 1.00 |
| G2FD035(S,H)14 | 1.00 | 1.00 | 1.00 |
| G2FD036(S,H)17 | 1.02 | 1.03 | 1.00 |
| G2FD036(S,H)21 | 1.03 | 1.03 | 1.00 |
| G2FD042(S,H)21 | 1.03 | 1.04 | 1.00 |
| G2FD046(S,H)17 | 1.05 | 1.05 | 1.01 |
Variable Speed | Coil | T.C. | S.C. | KW |
Furnace |
|
|
|
|
P1DUA12V | G1FA030S14 | 0.99 | 0.99 | 0.94 |
P1DUA12V | G2FD035(S,H)14 | 1.01 | 1.02 | 0.94 |
P1DUB16V | G1FA036S17 | 1.02 | 1.03 | 0.94 |
P1DUB16V | G2FD030(S,H)17 | 1.02 | 1.03 | 0.94 |
P1XDB12V | G2FD030(S,H)17 | 1.02 | 1.03 | 0.97 |
P1XUB12V | G1FA036S17 | 1.01 | 1.02 | 0.95 |
P1XUB12V | G2FD030(S,H)17 | 1.01 | 1.02 | 0.95 |
P1XUC16V | G1FA036S21 | 1.02 | 1.03 | 0.94 |
P1XUC16V | G2FD036(S,H)21 | 1.05 | 1.06 | 0.94 |
16 | Unitary Products Group |