TYPICAL INSTALLATION
| MINIMUM 18” SERVICE ACCESS | THERMOSTAT | TO FURNACE OR | |
60” OVERHEAD | CLEARANCE ON ONE SIDE | |||
| ||||
| AIR HANDLER | |||
CLEARANCE | WEATHERPROOF |
| ||
| TERMINAL BLOCK | |||
| DISCONNECT |
| ||
|
|
| ||
| SWITCH |
| NEC CLASS 1 WIRING | |
|
|
| NEC CLASS 2 WIRING | |
10” CLEARANCE |
|
| TO INDOOR COIL | |
COIL AREA |
|
|
NOTE: ALL OUTDOOR WIRING MUST BE WEATHERPROOF.
SEAL OPENING(S) WITH
PERMAGUM OR EQUIVALENT
CONTROL ACCESS PANEL
TYPICAL FIELD WIRING - 1 Phase Application
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
POWER WIRING
POWER WIRING
24 VOLT CONTROL WIRING |
| CONTROL WIRING | |
MINIMUM 18 GA. WIRE |
|
| |
|
| FACTORY WIRING | |
(NEC CLASS 2) |
|
| |
|
|
| |
| FURNACE OR AIR HANDLER TERMINAL BLOCK |
CONTACTOR
TERMINALS
GND.
LUGCOIL
CONDENSING UNIT
C Y R G W
* TERMINAL W IS ONLY REQUIRED ON SYSTEMS WITH HEAT.
*
Y R G W
ROOM THERMOSTAT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
TYPICAL FIELD WIRING - 3 Phase Application
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
GND.
LUG
POWER WIRING
CONTACTOR TERMINALS
COIL
24 VOLT CONTROL WIRING MINIMUM 18 GA. WIRE (NEC CLASS 2)
*TERMINAL W IS ONLY REQUIRED ON SYSTEMS WITH HEAT.
POWER WIRING
CONTROL WIRING
FACTORY WIRING
FURNACE OR AIR HANDLER TERMINAL BLOCK
C Y R G W
YR G W *
CONDENSING UNIT
ROOM THERMOSTAT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
Unitary Products Group | 13 |