Additional
Outdoor Unit |
| H2RC018S06 | H2RC024S06 | H2RC030S06 | H2RC036S06 | H2RC042S06 | H2RC048S06 | H4RC060S06 | |
Unit Orifice (s)1 |
| 53 | 59 | 63 | 73 | 78 | 87 | – | |
Factory | 4 - 9 | 4 - 7 | 5 - 8 | 5 - 3 | 6 - 13 | 7 - 7 | 8 - 15 | ||
Indoor Coil5 | Coil Orifice4 |
|
| Orifice or TXV | Kit 2 - Additional | Charge, Oz.3 |
|
| |
G1NA036S17L | 63 | – | – | 63 + 15 | 73 + 12 | – | – | – | |
– | – | 701 + 15 | 702 + 12 | – | – | – | |||
|
| ||||||||
G1NA048S21D | 78 | – | – | – | 73 + 12 | 78 + 0 | 87 + 0 | – | |
– | – | – | 702 + 12 | 702 + 0 | 703 + 0 | – | |||
|
| ||||||||
G1NA048S24P | 63 | – | – | – | 73 + 13 | 78 + 2 | 87 + 1 | – | |
– | – | – | 702 + 13 | 702 + 2 | 703 + 1 | – | |||
|
| ||||||||
G1NA060S24T | 78 | – | – | – | – | – | – | – | |
– | – | – | – | – | – | 703 + 0 | |||
|
| ||||||||
G1NF024SOF | 63 | – | – | – | – | – | – | – | |
– | – | – | – | – | – | – | |||
|
| ||||||||
G1NF036SOF | 67 | – | 59 + 12 | 63 + 0 | 73 + 7 | – | – | – | |
– | 701 + 12 | 701 + 0 | 702 + 7 | – | – | – | |||
|
| ||||||||
G1NF048SOF | 78 | – | – | – | – | 78 + 21 | 87 + 6 | – | |
– | – | – | – | 702 + 21 | 703 + 6 | – | |||
|
| ||||||||
G1NF060SOF | 87 | – | – | – | – | – | 87 + 18 | – | |
– | – | – | – | – | 703 + 18 | – | |||
|
| ||||||||
F(2,3)RP024N,H06(T) | 61 | 53 + 4 | 59 + 4 | – | – | – | – | – | |
701 + 4 | 701 + 4 | – | – | – | – | – | |||
|
| ||||||||
F(2,3)RP030N06(T) | 65 | – | 59 + 6 | 63 + 4 | – | – | – | – | |
– | 701 + 6 | 701 + 4 | – | – | – | – | |||
|
| ||||||||
F(2,3)RP036N06(T) | 75 | – | – | 63 + 4 | 73 + 8 | – | – | – | |
– | – | 701 + 4 | 702 + 8 | – | – | – | |||
|
| ||||||||
F(2,3)RP042N06(T) | 78 | – | – | – | 73 + 13 | 78 + 0 | – | – | |
– | – | – | 702 + 13 | 702 + 0 | – | – | |||
|
| ||||||||
F(2,3)FP048N06(T) | 84 | – | – | – | 73 + 16 | 78 + 10 | 87 + 11 | – | |
– | – | – | 702 + 16 | 702 + 10 | 703 + 11 | – | |||
|
| ||||||||
F(2,3)FP060N06(T) | 90 | – | – | – | – | – | 87 + 15 | – | |
– | – | – | – | – | 703 + 15 | 7035 + 5 | |||
|
| ||||||||
F(2,3)FV060N06(T) | 90 | – | – | – | – | – | 87 + 15 | – | |
– | – | – | – | – | 703 + 15 | 703 + 5 | |||
|
| ||||||||
FOOTNOTES: |
|
|
|
|
|
|
|
|
1.These orifices are factory mounted in the flow control device of each indoor coil and must be removed for TXV installation.
2.A TXV kit must be used with these coils to obtain system performance. (701,702,703 indicates 1TV07 ...series).
3.Systems matched with furnaces or air handlers not equipped with
4.These orifices are factory mounted in the flow control device of each indoor coil. A TXV is factory mounted if the model number has a (T) suffix.
5.This TXV is factory mounted in indoor coils, if the model number has a (T) suffix.
PROCEDURES:
1.Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and for 15 feet of interconnecting line tubing.
2.Verify the orifice size and additional charge required for specific evaporator coil in the system using the above table.
3.Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder for line set.
5.If the orifice in the evaporator was changed, verify the evaporator nameplate has been marked with the correct orifice size.
4 | Unitary Products Group |