York H*RC018 THRU 060 036-21137-004Rev. C, Unitary Products Group, Outdoor Unit, Unit Orifice s

Models: H*RC018 THRU 060 H*RC036S

1 24
Download 24 pages 41.1 Kb
Page 5
Image 5

 

 

 

 

 

 

 

036-21137-004 Rev. C (0505)

Additional R-22 Charge / Orifice Size for Various Matched Systems - 3 Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

H1RC036S

H1RC048S

 

H1RC060S

 

 

Unit Orifice (s) 1

 

 

 

 

 

 

Factory R-22 Charge, lbs-oz

 

 

6 - 2

7 - 10

 

9 - 3

 

 

Indoor Coil

Coil Orifice

 

 

TVX Kit2 = Additional Charge, Oz3

G2FD035(S,H)14

65

 

 

702 + 0

 

 

 

G2FD036(S,H)17,21

75

 

 

702 + 3

 

 

 

G2FD042(S,H)21

78

 

 

702 + 0

 

 

 

G2FD046(S,H)17

78

 

 

702 + 9

703 + 0

 

 

 

G2FD048(S,H)21,24

84

 

 

702 + 17

703 + 9

 

 

 

G2FD060(S,H)24

90

 

 

703 + 0

 

703 + 20

 

 

G2FD061H24

90

 

 

703 + 6

 

703 + 25

 

 

G1FA/G1UA036S14

73

 

 

702 + 1

 

 

 

G1FA/G1UA036S17,21

73

 

 

702 + 0

 

 

 

G1FA/G1UA048S17

84

 

 

703 + 2

 

 

 

G1FA/G1UA048S21

84

 

 

702 + 9

703 + 7

 

 

 

G1FA/G1UA060S21,24

90

 

 

703 + 14

 

703 + 20

 

 

G1NA036S17L

71

 

 

702 + 0

 

 

 

G1NA048S21D

78

 

 

702 + 0

703 + 0

 

 

 

G1NA048S24P

78

 

 

702 + 0

703 + 0

 

 

 

G1NA060S24T

87

 

 

 

703 + 0

 

 

G1NF036SOF

67

 

 

702 + 0

 

 

 

G1NF048SOF

78

 

 

702 + 0

 

 

 

G1NF060SOF

87

 

 

 

703 + 0

 

 

G1HD036

69

 

 

702 + 5

 

 

 

G1HD048

81

 

 

702 + 11

703 + 0

 

 

 

G1HD060

93

 

 

703 + 0

 

703 + 20

 

 

FOOTNOTES:

 

 

 

 

 

 

 

 

 

1.These orifices are factory mounted in the flow control device of each indoor coil and must be removed for TXV installation.

2.A TXV kit must be used with these coils to obtain system performance. (701,702,703 indicates 1TV07 ...series).

3.Systems matched with furnaces or air handlers not equipped with blower-off delays, may require blower Time Delay Kit #6918A5011.

PROCEDURES:

1.Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and for 15 feet of interconnecting line tubing.

2.Verify the orifice size and additional charge required for specific evaporator coil in the system using the above table.

3.Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.

4.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder

for line set.

5. If the orifice in the evaporator was changed, verify the evaporator nameplate has been marked with the correct orifice size.