York H*RC036S Physical and Electrical Data - 1 Phase, PHYSICAL AND ELECTRICAL DATA - 3 Phase

Models: H*RC018 THRU 060 H*RC036S

1 24
Download 24 pages 41.1 Kb
Page 2
Image 2

036-21137-004 Rev. C (0505)

Physical and Electrical Data - 1 Phase

MODEL

 

 

H2RC018S06

H2RC024S06

H2RC030S06

H2RC036S06

 

H2RC042S06

H2RC048S06

H4RC060S06

 

 

 

 

 

 

 

 

 

Unit Supply Voltage

 

 

 

 

208/230 – 1 – 60

 

 

 

Normal Voltage Range

 

 

 

 

187 to 252

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Circuit Ampacity1

10.1

14.1

16.5

 

19.7

 

26.2

28.5

37.5

Max. Overcurrent Device Amps 2

15

25

25

 

30

 

45

50

60

Compressor Type3

 

Recip

Inertia

Recip

 

Recip

 

ScrollB

Recip

ScrollB

Compressor Amps

Rated Load

7.7

10.9

12.8

 

14.7

 

19.9

21.8

28.8

Locked Rotor

48

60

68

 

82

 

115

105

145

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

No

No

No

 

Yes

 

No

No

No

 

 

 

 

 

 

 

 

 

 

 

Fan Motor Amps

Rated Load

0.5

0.5

0.5

 

1.3

 

1.3

1.3

1.5

 

 

 

 

 

 

 

 

 

 

 

Fan Diameter Inches

18

18

22

 

22

 

22

22

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated HP

1/12

1/12

1/15

 

1/4

 

1/4

1/4

1/4

Fan Motor

 

 

 

 

 

 

 

 

 

 

 

 

Nominal RPM

1,100

1,100

850

 

850

 

850

850

850

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal CFM

2,000

2,000

2,300

 

3,300

 

3,300

3,300

3,450

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Face Area Sq. Ft.

12.58

12.58

15.72

 

15.72

 

17.03

19.65

23.58

Coil

 

 

 

 

 

 

 

 

 

 

 

 

Rows Deep

1

1

1

 

1

 

1

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fin / Inches

18

18

18

 

18

 

18

18

22

 

 

 

 

 

 

 

 

 

 

 

 

Liquid Line OD

 

3/8

3/8

3/8

 

3/8

 

3/8

3/8

3/8

 

 

 

 

 

 

 

 

 

 

 

Vapor Line OD

 

3/4

3/4

3/4

 

3/4

 

7/8

7/8

1-1/8

 

 

 

 

 

 

 

 

 

 

Unit Charge (Lbs. - Oz.) 4

4 - 9

4 - 7

5 - 8

 

5 - 3

 

6 - 13

7 - 7

8 - 15

Charge Per Foot, Oz.

0.68

0.68

0.68

 

0.68

 

0.70

0.70

0.76

 

 

 

 

 

 

 

 

 

 

Operating Weight Lbs.

144

146

156

 

161

 

157

190

198

 

 

 

 

 

 

 

 

 

 

 

 

 

PHYSICAL AND ELECTRICAL DATA - 3 Phase

MODEL

 

 

H1RC036S25

H1RC048S25

H1RC060S25

 

H1RC036S46

H1RC048S46

H1RC060S46

Unit Supply Voltage

 

 

 

208/230 – 3 – 60

 

 

 

460 - 3 - 60

 

Normal Voltage Range 1

 

 

187 to 252

 

 

 

432 to 504

 

Minimum Circuit Ampacity

13.3

 

18.9

 

22.9

 

7.6

9.6

12.0

Max. Overcurrent Device Amps 2

20

 

30

 

40

 

15

15

20

Compressor Type

 

Inertia

 

Inertia

 

Scroll

 

Inertia

Inertia

Scroll

Compressor Amps

Rated Load

9.6

 

14.1

 

17.3

 

5.4

7.0

9.0

Locked Rotor

78.0

 

130.0

 

123.0

 

40.0

64.0

62.0

 

 

 

 

 

 

Crankcase Heater

 

No

 

No

 

No

 

No

No

No

Fan Motor Amps

Rated Load

1.3

 

1.3

 

1.3

 

0.8

0.8

0.8

Fan Diameter Inches

22

 

22

 

22

 

22

22

22

 

 

 

Rated HP

1/4

 

1/4

 

1/4

 

1/4

1/4

1/4

Fan Motor

 

Nominal RPM

850

 

850

 

850

 

850

850

850

 

 

 

Nominal CFM

3,300

 

3,300

 

3,400

 

3,300

3,300

3,400

 

 

Face Area Sq. Ft.

15.72

 

17.03

 

23.58

 

15.72

17.03

23.58

Coil

 

Rows Deep

1

 

1

 

1

 

1

1

1

 

 

Fin / Inches

18

 

18

 

18

 

18

18

18

Liquid Line OD

 

3/8

 

3/8

 

3/8

 

3/8

3/8

3/8

Vapor Line OD

 

3/4

 

7/8

 

1-1/8

 

3/4

7/8

1-1/8

Unit Charge (Lbs. - Oz.) 4

6 - 2

 

7 - 10

 

9 - 3

 

6 - 2

7 - 10

9 - 3

Charge Per Foot, Oz.

0.68

 

0.70

 

0.76

 

0.68

0.70

0.76

Operating Weight Lbs.

157

 

184

 

198

 

157

184

198

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Rated in accordance with ARI Standard 110, utilization range “A”.

2.Dual element fuses or HACR circuit breaker.

3.All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.

4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or sub- tract the amount of refrigerant, using the difference in length multiplied by the per foot value.

2

Unitary Products Group

Page 2
Image 2
York H*RC036S warranty Physical and Electrical Data - 1 Phase, PHYSICAL AND ELECTRICAL DATA - 3 Phase, 036-21137-004Rev. C