COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

H2RC048S06

 

 

 

 

 

 

 

INDOOR COIL MODEL NO.

 

G1FA048S21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDENSING

IDCFM

 

1375

 

 

1575

 

 

1775

 

 

 

 

 

 

 

 

 

 

 

ENTERING AIR

ID DB (°F)

85

80

75

85

80

75

85

80

75

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

ID WB (°F)

72

67

63

72

67

63

72

67

63

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

52.8

49.9

45.4

53.5

50.6

46.8

54.2

51.3

48.2

75

 

 

 

 

 

 

 

 

 

 

S.C.

33.3

32.7

31.5

34.9

34.5

33.6

36.5

36.2

35.7

 

 

 

 

 

 

 

 

 

 

 

 

KW

3.14

3.09

3.03

3.15

3.10

3.04

3.17

3.12

3.06

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

50.9

47.1

42.4

51.6

48.1

43.5

52.3

49.1

44.7

85

 

 

 

 

 

 

 

 

 

 

S.C.

33.3

32.0

30.4

35.3

34.2

32.6

37.4

36.3

34.7

 

 

 

 

 

 

 

 

 

 

 

 

KW

3.44

3.35

3.30

3.46

3.38

3.31

3.47

3.40

3.32

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

49.0

44.3

39.4

49.7

45.5

40.3

50.3

46.8

41.2

95

 

 

 

 

 

 

 

 

 

 

S.C.

33.2

31.2

29.3

35.8

34.1

31.5

38.4

36.5

33.7

 

 

 

 

 

 

 

 

 

 

 

 

KW

3.74

3.62

3.57

3.76

3.56

3.57

3.78

3.69

3.58

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

44.7

40.0

35.8

45.4

41.0

36.5

46.1

42.0

37.1

105

 

 

 

 

 

 

 

 

 

 

S.C.

31.9

29.8

27.8

34.5

32.2

29.9

37.0

34.7

32.1

 

 

 

 

 

 

 

 

 

 

 

 

KW

4.01

3.89

3.80

4.04

3.91

3.81

4.07

3.94

3.83

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

40.5

35.7

32.1

41.2

36.5

32.6

41.9

37.2

33.1

115

 

 

 

 

 

 

 

 

 

 

S.C.

30.5

28.3

26.3

33.1

30.5

28.4

35.7

32.8

30.5

 

 

 

 

 

 

 

 

 

 

 

 

KW

4.28

4.15

4.02

4.32

4.17

4.05

4.35

4.19

4.08

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

36.3

31.3

28.5

36.9

31.9

28.8

37.6

32.5

29.1

125

 

 

 

 

 

 

 

 

 

 

S.C.

29.2

26.8

24.8

31.8

28.9

26.8

34.4

31.0

28.8

 

 

 

 

 

 

 

 

 

 

 

 

KW

4.55

4.42

4.25

4.60

4.43

4.29

4.64

4.44

4.33

 

 

 

 

 

 

 

 

 

 

 

NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.

Air Handler

Coil

T.C.

S.C.

KW

 

 

 

 

 

F2FP048

 

1.00

1.00

1.02

 

 

 

 

 

F2FP060

 

1.03

1.03

1.06

 

 

 

 

 

F2FV060

 

1.06

1.10

0.95

 

 

 

 

 

N1AHC1606

G2FD048(S,H)21,24

1.00

1.00

1.01

 

 

 

 

 

N1AHD2006

G2FD060(S,H)24

1.03

1.03

1.02

 

 

 

 

 

N1AHD2006

G2FD061H24

1.04

1.04

1.02

 

 

 

 

 

N1VSC16

G2FD048(S,H)21

1.01

1.02

0.97

 

 

 

 

 

N1VSD20

G2FD060(S,H)24

1.04

1.06

0.99

 

 

 

 

 

N1VSD20

G2FD061H24

1.05

1.07

0.99

 

 

 

 

 

 

G1FA048S17

0.98

0.98

0.98

 

 

 

 

 

 

G1FA060S21,24

1.03

1.03

1.02

 

 

 

 

 

 

G1HD048

0.99

0.99

1.01

 

 

 

 

 

 

G1HD060

1.02

1.02

1.02

 

 

 

 

 

 

G1NA048S21D

0.99

0.99

1.02

 

 

 

 

 

 

G1UA048S17

0.98

0.98

0.98

 

 

 

 

 

 

G1UA048S21

1.00

1.00

1.00

 

 

 

 

 

 

G1UA060S21,24

1.03

1.03

1.02

 

 

 

 

 

 

G2FD046(S,H)17

0.98

0.98

1.00

 

 

 

 

 

 

G2FD048(S,H)21,24

1.00

1.00

1.01

 

 

 

 

 

 

G2FD060(S,H)24

1.03

1.03

1.02

 

 

 

 

 

 

G2FD061H24

1.04

1.04

1.02

 

 

 

 

 

Variable Speed

Coil

T.C.

S.C.

KW

Furnace

 

 

 

 

P1DUC20V

G1FA048S21

1.00

1.00

0.99

 

 

 

 

 

P1DUC20V

G2FD048(S,H)21

1.00

1.00

1.00

 

 

 

 

 

P1XDD20V

G2FD048(S,H)24

1.01

1.01

1.01

 

 

 

 

 

P1XUC16V

G1FA048S21

0.99

0.99

1.00

 

 

 

 

 

P1XUC16V

G2FD048(S,H)21

0.99

0.98

1.01

 

 

 

 

 

P1XUC20V

G1FA048S21

1.00

1.00

0.99

 

 

 

 

 

P1XUC20V

G2FD048(S,H)21

1.00

1.00

1.00

 

 

 

 

 

P1XUD20V

G1FA060S24

1.04

1.05

1.00

 

 

 

 

 

P1XUD20V

G2FD048(S,H)24

1.01

1.01

0.99

 

 

 

 

 

P1XUD20V

G2FD060(S,H)24

1.04

1.05

1.00

 

 

 

 

 

20