York K3EU180 Keu Electrical Data Continued, Model TONS, Power, Indoor, Heater, Nominal, Hacr

Models: K3EU180 K4EU090 K3EU120 K2EU060

1 28
Download 28 pages 18.44 Kb
Page 23
Image 23
TABLE 22: KEU ELECTRICAL DATA (CONTINUED)

036-21300-002-A-0905

TABLE 22: KEU ELECTRICAL DATA (CONTINUED)

Model

(TONS)

180

(15)

Power

Indoor

Heater

Nominal

 

 

Min.

Max. Fuse1 /

Applied

Electric

Circuit

HACR

Supply

Motor

Model

Heater

Heater KW

Heat Amps

Ampacity

Breaker2

Voltage

FLA

Number

KW

 

 

(AMPS)

(AMPS)

 

 

 

 

 

 

 

 

None

--

--

--

13.3

20

 

 

2HS04501025

10

7.5

20.8

39.3

40

208

10.6

2HS04501625

16

12.0

33.4

54.9

60

2HS04502625

26

19.5

54.2

81.0

90

 

 

 

 

2HS04503625

36

27.0

75.1

107.1

110

 

 

2HS04507225

72

54.1

150.1

200.9

225

 

 

None

--

--

--

12.0

15

 

 

2HS04501025

10

10.0

24.1

42.1

45

240

9.6

2HS04501625

16

16.0

38.5

60.1

70

2HS04502625

26

26.0

62.5

90.2

100

 

 

 

 

2HS04503625

36

36.0

86.6

120.3

125

 

 

2HS04507225

72

72.0

173.2

228.5

250

 

 

None

--

--

--

6.0

15

 

 

2HS04501046

10

10.0

12.0

21.0

25

460

4.8

2HS04501646

16

16.0

19.2

30.1

35

2HS04502646

26

26.0

31.3

45.1

50

 

 

 

 

2HS04503646

36

36.0

43.3

60.1

70

 

 

2HS04507246

72

72.0

86.6

114.3

125

 

 

None

--

--

--

4.9

15

 

 

2HS04501058

10

10.0

9.6

16.9

20

575

3.9

2HS04501658

16

16.0

15.4

24.1

25

2HS04502658

26

26.0

25.0

36.1

40

 

 

 

 

2HS04503658

36

36.0

34.6

48.2

50

 

 

2HS04507258

72

72.0

69.3

91.5

100

 

 

 

 

 

 

 

 

1.Dual element time delay.

2.HACR type per NEC.

3.The K*EU060 indoor motor is single phase. The electrical heaters MUST be supplied with 3-phase voltage only.

Unitary Products Group

23

Page 23
Image 23
York K3EU180, K2EU060, K3EU120 Keu Electrical Data Continued, Model TONS, Power, Indoor, Heater, Nominal, Max. Fuse1, Hacr