UNITSWITHELECTRICHEATACCESSORY

036-21300-002-A-0905

UNITSWITHELECTRICHEATACCESSORY

TERMINALBLOCK4TB

24-VOLTCONTROLWIRING ONBLOWERUNIT

R

 

R

Y1

 

Y

Y2

1

O

W1

 

66

W2

2

60

1

TO

COND.

UNIT

NOTES:

1Onlyrequiredfor2-stagecooling.**

2Notrequiredon10KW heaters(onlyone-stageheating). 3Thisthermostatandsub-basemustbeusedwhenever ablowerunitisequippedwithanelectricheataccessory.

 

G

53

 

 

 

G

TERMINALSON

THERMOSTAT6TH047015243

 

WITHSUB-BASE2TB04700324

B

JUMPER

Anoutdoorthermostatcan bewiredbetweenterminals 53and60toprovideaddi- tionalstagingon36and 72KW heaters.

Thefieldwiringconnectedtothesedummy terminalson4TBcanberouteddirectlyfrom thecondensingunittothetermostatifdesired.

NOTE:TerminalRon4TBisnotadummyterminalon KEU060unitsbecausetheseunitsincludeatransform- erthatpowersthecontrolcircuit.Onlargersystems, thistransformerissuppliedwiththecondensingunit.

*WireRon4TBterminalblockisnotrequiredon5tonunit. **OnlyappliestoHCA180/KEU180systemswhentheHCA180is equippedwiththecapacityreductionaccessory.Two115-volt wireswilalsoberequiredfortheliquidlinesolenoidvalve thatwilbefurnishedwiththecapacityreductionaccessory.

RefertoForm550.13N1.5foradditionalinformationon thisaccessory.

FIGURE 13 - FIELD WIRING FOR UNITS WITH ELECTRIC HEAT