ZF120 (10 Ton) (Continued)
Air on |
|
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
|
| |||||
Evaporator Coil | Total | Total |
| Sensible Capacity (MBh) |
| Total | Total |
| Sensible Capacity (MBh) |
| ||||||||
CFM |
| WB | Capacity1 | Input |
| Return Dry Bulb (°F) |
| Capacity1 | Input |
| Return Dry Bulb (°F) |
| ||||||
| (°F) | (MBh) | (kW)2 |
|
|
|
|
|
| (MBh) | (kW)2 |
|
|
|
|
|
| |
| 90 | 85 | 80 | 75 | 70 | 65 | 90 | 85 | 80 | 75 | 70 | 65 | ||||||
|
|
|
|
|
| 115°F |
|
|
|
|
|
|
| 125°F |
|
|
|
|
|
| 77 | 117.2 | 11.2 | 54.3 | 43.9 | 33.2 | - | - | - | 104.6 | 12.1 | 64.4 | 42.9 | 31.5 | - | - | - |
2500 |
| 72 | 106.1 | 10.8 | 74.7 | 63.9 | 53.2 | 42.5 | - | - | 94.9 | 11.6 | 74.8 | 64.0 | 53.3 | 42.6 | - | - |
| 67 | 95.0 | 10.4 | 95.0 | 84.0 | 73.3 | 62.6 | 51.8 | - | 85.2 | 11.1 | 85.2 | 85.2 | 75.2 | 64.5 | 53.8 | - | |
|
| |||||||||||||||||
|
| 62 | 85.5 | 10.1 | 85.5 | 85.5 | 81.6 | 70.9 | 60.1 | 49.4 | 76.3 | 10.8 | 76.3 | 76.3 | 76.3 | 70.2 | 59.4 | 48.7 |
|
| 77 | 120.1 | 11.2 | 64.1 | 47.2 | 34.5 | - | - | - | 106.6 | 12.3 | 71.1 | 45.8 | 31.5 | - | - | - |
|
| 72 | 108.7 | 10.9 | 80.7 | 68.1 | 55.4 | 42.7 | - | - | 96.7 | 11.7 | 78.9 | 66.3 | 53.7 | 41.0 | - | - |
3000 |
| 67 | 97.4 | 10.5 | 97.4 | 88.9 | 76.3 | 63.6 | 51.0 | - | 86.8 | 11.2 | 86.8 | 86.8 | 75.9 | 63.2 | 50.6 | - |
|
| 62 | 87.5 | 10.2 | 87.5 | 87.5 | 87.5 | 74.9 | 62.2 | 49.6 | 77.7 | 10.9 | 77.7 | 77.7 | 77.7 | 72.6 | 60.0 | 47.3 |
|
| 57 | 90.8 | 10.3 | 90.8 | 90.8 | 87.8 | 75.2 | 62.5 | 49.8 | 83.7 | 11.0 | 83.7 | 83.7 | 83.7 | 72.1 | 59.4 | 46.8 |
|
| 77 | 122.9 | 11.3 | 73.9 | 50.5 | 35.9 | - | - | - | 108.6 | 12.4 | 77.9 | 48.7 | 31.5 | - | - | - |
|
| 72 | 111.3 | 10.9 | 86.8 | 72.2 | 57.6 | 43.0 | - | - | 98.5 | 11.8 | 83.1 | 68.6 | 54.0 | 39.4 | - | - |
3500 |
| 67 | 99.7 | 10.6 | 99.7 | 93.9 | 79.3 | 64.7 | 50.1 | - | 88.4 | 11.3 | 88.4 | 88.4 | 76.5 | 62.0 | 47.4 | - |
|
| 62 | 89.6 | 10.3 | 89.6 | 89.6 | 93.5 | 78.9 | 64.3 | 49.7 | 79.2 | 11.0 | 79.2 | 79.2 | 79.2 | 75.0 | 60.5 | 45.9 |
|
| 57 | 93.0 | 10.4 | 93.0 | 93.0 | 91.3 | 76.7 | 62.1 | 47.5 | 85.3 | 11.1 | 85.3 | 85.3 | 85.2 | 70.6 | 56.1 | 41.5 |
|
| 77 | 125.8 | 11.4 | 83.7 | 53.8 | 37.2 | - | - | - | 110.6 | 12.5 | 84.6 | 51.6 | 31.5 | - | - | - |
|
| 72 | 113.9 | 11.0 | 92.9 | 76.3 | 59.8 | 43.2 | - | - | 100.3 | 11.9 | 87.3 | 70.8 | 54.3 | 37.8 | - | - |
4000 |
| 67 | 102.0 | 10.6 | 102.0 | 98.8 | 82.3 | 65.7 | 49.2 | - | 90.0 | 11.4 | 90.0 | 90.0 | 77.2 | 60.7 | 44.2 | - |
|
| 62 | 91.7 | 10.4 | 91.7 | 91.7 | 99.5 | 82.9 | 66.4 | 49.8 | 80.6 | 11.1 | 80.6 | 80.6 | 80.6 | 77.4 | 61.0 | 44.5 |
|
| 57 | 95.1 | 10.5 | 95.1 | 95.1 | 94.7 | 78.2 | 61.6 | 45.1 | 86.9 | 11.2 | 86.9 | 86.9 | 85.7 | 69.2 | 52.7 | 36.2 |
|
| 72 | 115.9 | 11.1 | 99.2 | 81.4 | 63.6 | 45.8 | - | - | 102.2 | 12.0 | 93.1 | 75.4 | 57.7 | 40.1 | - | - |
4500 |
| 67 | 103.8 | 10.7 | 103.8 | 102.2 | 87.6 | 69.8 | 52.0 | - | 91.7 | 11.5 | 91.7 | 91.7 | 82.0 | 64.4 | 46.7 | - |
| 62 | 93.3 | 10.4 | 93.3 | 93.3 | 97.2 | 79.4 | 61.6 | 43.8 | 82.2 | 11.1 | 82.2 | 82.2 | 82.2 | 71.2 | 53.5 | 35.8 | |
|
| |||||||||||||||||
|
| 57 | 96.8 | 10.5 | 96.8 | 96.8 | 96.6 | 78.8 | 61.0 | 43.2 | 88.5 | 11.3 | 88.5 | 88.5 | 87.9 | 70.3 | 52.6 | 34.9 |
|
| 72 | 117.9 | 11.1 | 105.5 | 86.5 | 67.4 | 48.4 | - | - | 104.2 | 12.1 | 98.9 | 80.0 | 61.2 | 42.3 | - | - |
5000 |
| 67 | 105.6 | 10.7 | 105.6 | 105.6 | 92.8 | 73.8 | 54.7 | - | 93.5 | 11.5 | 93.5 | 93.5 | 86.9 | 68.0 | 49.2 | - |
| 62 | 95.0 | 10.5 | 95.0 | 95.0 | 95.0 | 75.9 | 56.8 | 37.8 | 83.7 | 11.2 | 83.7 | 83.7 | 83.7 | 64.9 | 46.0 | 27.2 | |
|
| |||||||||||||||||
|
| 57 | 98.5 | 10.6 | 98.5 | 98.5 | 98.5 | 79.4 | 60.4 | 41.3 | 90.2 | 11.3 | 90.2 | 90.2 | 90.2 | 71.4 | 52.5 | 33.7 |
1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
24 | Johnson Controls Unitary Products |