York R-410A manual Sound Performance, Electric Heat Multipliers, Indoor Sound Power Levels

Models: R-410A

1 68
Download 68 pages 3.65 Kb
Page 35
Image 35
Electric Heat Multipliers

528194-YTG-F-1210

Electric Heat Multipliers

 

Voltage

kW Capacity Multipliers1

Nominal

 

Applied

 

 

240

 

208

0.75

 

230

0.92

 

 

480

 

460

0.92

600

 

575

0.92

1.Electric heaters are rated at nominal voltage. Use this table to determine the electric heat capacity for heaters applied at lower voltages.

Sound Performance

Indoor Sound Power Levels

Size

 

 

ESP

Blower

 

 

Sound Power, dB (10-12) Watts

 

 

Model

CFM

Sound Rating1

 

Octave Band Centerline Frequency (Hz)

 

(Tons)

(IWG)

 

 

 

 

 

 

RPM

BHP

dB (A)

63

125

250

500

1000

2000

4000

8000

 

 

 

 

078

ZF

2600

0.6

812

1.14

74

71

73

73

71

69

65

65

60

(6.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

090

ZF

3000

0.6

854

1.47

77

74

76

76

74

72

68

68

63

(7.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

102

ZF

3400

0.6

872

1.65

80

77

79

79

77

75

71

71

66

(8.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

ZF

4000

0.6

959

2.29

83

80

82

82

80

78

74

74

69

(10)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150

ZF

5000

0.6

1132

3.74

87

84

86

86

84

82

78

78

73

(12.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data in any other form than sound power level ratings.

Outdoor Sound Power Levels

ZF078-150

Size

Model

Sound Rating1

 

 

Octave Band Centerline Frequency (Hz)

 

 

(Tons)

dB (A)

63

125

250

500

1000

2000

4000

8000

 

078

ZF

84

86.0

87.5

86.0

82.5

79.0

73.5

68.5

62.0

(6.5)

 

 

 

 

 

 

 

 

 

 

090

ZF

89

89.5

92.0

89.0

87.5

84.0

78.5

73.5

66.5

(7.5)

 

 

 

 

 

 

 

 

 

 

102

ZF

91

91.5

93.5

92.5

89.0

85.5

80.5

76.0

71.0

(8.5)

 

 

 

 

 

 

 

 

 

 

120

ZF

92

99.5

94.5

92.0

90.0

87.0

81.0

76.0

70.0

(10)

 

 

 

 

 

 

 

 

 

 

150

ZF

88

91.0

92.5

90.0

85.0

81.5

77.0

73.0

66.5

(12.5)

 

 

 

 

 

 

 

 

 

 

1. Rated in accordance with ARI 270 standard.

Johnson Controls Unitary Products

35

Page 35