York R-410A manual ZF120 10 Ton Side Duct, ZF150 12.5 Ton Side Duct

Models: R-410A

1 68
Download 68 pages 3.65 Kb
Page 28
Image 28
ZF120 (10 Ton) Side Duct

528194-YTG-F-1210

ZF120 (10 Ton) Side Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

0.2

 

0.4

0.6

0.8

1.0

1.2

 

1.4

1.6

 

1.8

 

2.0

 

(CFM)

 

 

 

 

 

RPM BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

 

 

Field Supplied Drive

 

 

 

Standard 2 HP & Drive

 

 

 

Hi Static 3 HP & Drive

 

2600

675

0.53

726

0.74

776

0.94

824

1.12

870

1.30

914

1.48

957

1.65

1000

1.82

1041

1.99

1082

2.17

2800

686

0.63

738

0.84

787

1.04

835

1.23

881

1.41

925

1.58

969

1.76

1011

1.93

1052

2.10

1093

2.27

3000

699

0.75

750

0.96

800

1.16

847

1.34

893

1.52

938

1.70

981

1.87

1024

2.04

1065

2.21

1106

2.39

3200

713

0.88

764

1.09

814

1.28

861

1.47

907

1.65

952

1.83

995

2.00

1037

2.17

1079

2.34

1119

2.52

3400

728

1.02

779

1.23

829

1.43

877

1.61

923

1.79

967

1.97

1010

2.14

1053

2.31

1094

2.48

1135

2.66

3600

745

1.18

796

1.39

846

1.59

893

1.77

939

1.95

984

2.13

1027

2.30

1069

2.47

1111

2.64

1152

2.82

3800

763

1.36

815

1.57

864

1.76

912

1.95

958

2.13

1002

2.31

1046

2.48

1088

2.65

1129

2.82

1170

3.00

4000

783

1.55

835

1.76

884

1.96

932

2.15

978

2.33

1022

2.50

1066

2.67

1108

2.84

1149

3.02

1190

3.19

4200

805

1.77

856

1.98

906

2.17

953

2.36

999

2.54

1044

2.72

1087

2.89

1129

3.06

1171

3.23

1211

3.41

4400

828

2.00

879

2.21

929

2.41

976

2.59

1022

2.77

1067

2.95

1110

3.12

1152

3.29

-

-

-

-

4600

852

2.25

904

2.46

953

2.66

1001

2.85

1047

3.03

1092

3.20

1135

3.37

-

-

-

-

-

-

4800

879

2.52

930

2.73

980

2.93

1027

3.12

1073

3.30

-

-

-

-

-

-

-

-

-

-

5000

906

2.81

958

3.02

1007

3.22

1055

3.41

-

-

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 HP & Field Supplied Drive

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

ZF150 (12.5 Ton) Side Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

 

1.8

 

2.0

 

(CFM)

 

 

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

 

 

 

 

3 HP & Field

Supplied Drive

 

 

 

 

 

Standard 3 HP & Drive

 

 

 

 

 

3200

684

1.00

741

1.16

794

1.32

844

1.48

892

1.65

940

1.81

988

1.97

1036

2.12

1087

2.27

1141

2.42

3400

709

1.15

765

1.30

818

1.46

868

1.62

916

1.79

964

1.95

1012

2.11

1061

2.26

1112

2.42

1166

2.56

3600

734

1.30

791

1.46

844

1.62

894

1.78

942

1.94

990

2.10

1038

2.26

1087

2.42

1137

2.57

1191

2.72

3800

761

1.48

818

1.63

871

1.79

921

1.95

969

2.12

1017

2.28

1065

2.44

1114

2.59

1164

2.75

1218

2.89

4000

789

1.66

846

1.82

899

1.98

949

2.14

997

2.31

1045

2.47

1093

2.63

1142

2.78

1192

2.93

1246

3.08

4200

818

1.87

875

2.03

928

2.19

978

2.35

1026

2.51

1074

2.67

1121

2.83

1170

2.99

1221

3.14

1275

3.29

4400

847

2.09

904

2.25

957

2.41

1007

2.57

1055

2.73

1103

2.90

1151

3.06

1199

3.21

1250

3.36

1304

3.51

4600

877

2.33

934

2.49

986

2.65

1036

2.81

1085

2.97

1132

3.14

1180

3.29

1229

3.45

1280

3.60

1334

3.75

4800

907

2.59

963

2.75

1016

2.91

1066

3.07

1115

3.23

1162

3.39

1210

3.55

1259

3.71

1310

3.86

1364

4.01

5000

937

2.86

993

3.02

1046

3.18

1096

3.34

1145

3.50

1192

3.66

1240

3.82

1289

3.98

1340

4.13

1394

4.28

5200

967

3.15

1023

3.31

1076

3.47

1126

3.63

1175

3.79

1222

3.95

1270

4.11

1319

4.27

1370

4.42

1424

4.57

5400

997

3.45

1053

3.61

1106

3.77

1156

3.93

1205

4.09

1252

4.26

1300

4.41

1349

4.57

1400

4.72

1454

4.87

5600

1027

3.77

1083

3.93

1136

4.09

1186

4.25

1235

4.41

1282

4.57

1330

4.73

1379

4.89

1430

5.04

1484

5.19

5800

1057

4.11

1113

4.26

1166

4.42

1216

4.59

1264

4.75

1312

4.91

1360

5.07

1409

5.22

-

-

-

-

6000

1086

4.46

1143

4.61

1196

4.77

1246

4.93

1294

5.10

1342

5.26

-

-

-

-

-

-

-

-

6200

1116

4.82

1172

4.98

1225

5.14

1275

5.30

-

-

-

-

-

-

-

-

-

-

-

-

 

 

 

Hi Static 5 HP & Drive

 

 

 

 

 

 

5 HP & Field Supplied Drive

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

28

Johnson Controls Unitary Products

Page 28
Image 28
York R-410A manual ZF120 10 Ton Side Duct, ZF150 12.5 Ton Side Duct