528194-YTG-F-1210

RPM Selection

Size

Model

HP

Max

Motor

Blower

6 Turns

5 Turns

4 Turns

3 Turns

2 Turns

1 Turn

Fully

(Tons)

BHP

Sheave

Sheave

Open

Open

Open

Open

Open

Open

Closed

 

 

078

ZF

1.5

1.73

1VM50

AK74

N/A

887

936

986

1035

1084

1134

(6.5)

2

2.30

1VM50

AK64

N/A

1039

1094

1150

1207

1256

1308

 

090

ZF

1.5

1.73

1VM50

AK74

N/A

887

936

986

1035

1084

1134

(7.5)

3

3.45

1VM50

AK61

N/A

1088

1147

1205

1265

1312

1365

 

102

ZF

2

2.30

1VM50

AK94

N/A

690

728

767

805

843

882

(8.5)

3

3.45

1VM50

AK74

N/A

887

936

986

1035

1084

1134

 

120

ZF

2

2.30

1VM50

AK84

N/A

776

819

863

906

949

992

(10)

3

3.45

1VM50

AK74

N/A

887

936

986

1035

1084

1134

 

150

ZF

3

3.45

1VM50

AK74

N/A

887

936

986

1035

1084

1134

(12.5)

5

5.75

1VP56

BK77

1052

1095

1136

1175

1216

1272

N/A

 

Additional Static Resistance

Size

Model

CFM

Cooling Only1

Economizer2,3

4” Filter2

 

Electric Heat kW2

 

(Tons)

9

18

24

36

54

 

 

 

 

 

 

 

1900

0.00

0.07

0.10

0.05

0.06

0.07

0.08

0.10

 

 

2100

-0.01

0.09

0.11

0.06

0.07

0.08

0.09

0.11

 

 

2300

-0.01

0.11

0.12

0.07

0.08

0.09

0.10

0.13

 

 

2500

-0.02

0.13

0.14

0.08

0.09

0.10

0.11

0.14

 

 

2700

-0.03

0.16

0.15

0.09

0.10

0.12

0.13

0.16

 

 

2900

-0.04

0.18

0.16

0.10

0.11

0.13

0.14

0.18

078 (6.5)

ZF

3100

-0.05

0.20

0.18

0.12

0.13

0.15

0.16

0.20

090 (7.5)

3300

-0.06

0.22

0.19

0.13

0.14

0.17

0.18

0.22

 

 

 

3500

-0.07

0.24

0.20

0.15

0.16

0.19

0.20

0.24

 

 

3700

-0.08

0.27

0.21

0.17

0.18

0.21

0.22

0.26

 

 

3900

-0.09

0.29

0.23

0.19

0.20

0.23

0.24

0.28

 

 

4100

-0.09

0.31

0.24

0.21

0.22

0.25

0.26

0.31

 

 

4300

-0.10

0.30

0.25

0.23

0.24

0.28

0.29

0.34

 

 

4500

-0.11

0.35

0.26

0.25

0.26

0.30

0.31

0.37

 

 

1900

0.06

0.02

0.12

0.05

0.06

0.07

0.08

0.10

 

 

2100

0.07

0.02

0.13

0.06

0.07

0.08

0.09

0.11

 

 

2300

0.08

0.02

0.14

0.07

0.08

0.09

0.10

0.13

 

 

2500

0.09

0.02

0.16

0.08

0.09

0.10

0.11

0.14

 

 

2700

0.11

0.03

0.17

0.09

0.10

0.12

0.13

0.16

 

 

2900

0.12

0.03

0.19

0.10

0.11

0.13

0.14

0.18

 

 

3100

0.14

0.03

0.20

0.12

0.13

0.15

0.16

0.20

 

 

3300

0.16

0.03

0.22

0.13

0.14

0.17

0.18

0.22

 

 

3500

0.18

0.04

0.26

0.15

0.16

0.19

0.20

0.24

 

 

3700

0.20

0.04

0.27

0.17

0.18

0.21

0.22

0.26

102 (8.5)

 

3900

0.23

0.04

0.29

0.19

0.20

0.23

0.24

0.28

120 (10)

ZF

4100

0.25

0.04

0.32

0.21

0.22

0.25

0.26

0.31

150 (12.5)

 

4300

0.28

0.05

0.35

0.23

0.24

0.28

0.29

0.34

 

 

4500

0.30

0.05

0.38

0.25

0.26

0.30

0.31

0.37

 

 

4700

0.33

0.05

0.41

0.28

0.29

0.33

0.34

0.40

 

 

4900

0.36

0.05

0.44

0.30

0.31

0.35

0.37

0.43

 

 

5100

0.39

0.06

0.47

0.33

0.34

0.38

0.40

0.46

 

 

5300

0.42

0.06

0.51

0.35

0.37

0.41

0.43

0.49

 

 

5500

0.45

0.06

0.55

0.38

0.40

0.44

0.46

0.53

 

 

5700

0.48

0.06

0.58

0.41

0.43

0.47

0.49

0.56

 

 

5900

0.52

0.07

0.62

0.44

0.46

0.50

0.53

0.59

 

 

6100

0.56

0.07

0.67

0.47

0.49

0.53

0.56

0.62

 

 

6300

0.60

0.07

0.71

0.50

0.53

0.56

0.59

0.65

1.Add these values to the available static resistance in the respective Blower Performance Tables.

2.Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.

3.The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

Johnson Controls Unitary Products

31

Page 31
Image 31
York R-410A manual RPM Selection, Additional Static Resistance, Cfm

R-410A specifications

York R-410A is a widely recognized and highly efficient refrigerant used in modern air conditioning systems. Developed as an environmentally friendly alternative to R-22, R-410A has gained popularity in the HVAC industry due to its numerous advantageous features and characteristics.

One of the main features of York R-410A is its ability to provide superior cooling performance. This refrigerant operates efficiently at both high and low temperatures, allowing systems using it to maintain optimal indoor climates even during extreme weather conditions. Its high energy efficiency ratio (EER) and seasonal energy efficiency ratio (SEER) ratings make it a preferred choice for energy-conscious consumers, resulting in lower energy bills and a reduced carbon footprint.

Technologically, York R-410A systems feature advanced compressor designs that enhance their overall reliability and performance. These compressors are often equipped with variable-speed technology, enabling them to adjust their output to match the cooling demands of the space. This not only improves comfort levels but also leads to efficient energy consumption, reducing wear and tear on the equipment over time.

Another significant characteristic of York R-410A is its non-ozone-depleting properties. Unlike its predecessor R-22, which is being phased out due to its damaging effects on the ozone layer, R-410A is designed to minimize environmental impact. Its lower global warming potential (GWP) further underscores its role in promoting sustainability within the HVAC sector.

Furthermore, York R-410A systems are engineered with enhanced safety features. The refrigerant is non-toxic and non-flammable, which makes it safer for use in both residential and commercial applications. Additionally, its high thermal stability reduces the risk of breakdown or leakage, contributing to longer system lifespans and lower maintenance costs.

In conclusion, York R-410A stands out as a cutting-edge refrigerant that combines efficiency, safety, and environmental responsibility. With its advanced technologies and remarkable characteristics, it meets the demands of modern air conditioning requirements while paving the way for a sustainable future in HVAC systems. Adopting York R-410A not only benefits individual users through improved comfort and lower energy bills but also plays a vital role in protecting our planet's ozone layer and mitigating climate change.