Dimensions – English

Dimensions – English

Models YCIV0157E/V and YCIV0157S/P

 

CONTROL ENTRY

 

3" WIDE X 13 1/2" HIGH

 

1 1/2"

4"

POWER ENTRY

10" WIDE X 13" HIGH

VIEW B-B

1 3/4"

 

Models YCIV0157E/V and YCIV0157S/P 12"

POWER ENTRY IS ON BOTTOM OF PANEL

C

VIEW C-C

BB

C

A

 

B (EDGE OF UNIT

 

 

 

 

TO COOLER

 

 

 

 

CONNECTION)

 

 

 

 

 

 

88 1/8"

 

 

 

 

VIEW A-A

YCIV

A

B

C

D

0157E/V

19.1"

28.1"

84.5"

112.8"

0157S/P

17.4"

29.1"

90.0"

110.1"

Notes:

1.Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air patters and possible diminished performance. Johnson Controls’ unit controls will optimize the operation without nuisance high pressure safety cutouts; however, the system designer MUST consider potential performance degradation.

Access to the unit control center stipulates the unit is no higher than on spring isolators. Recommended minimum clearances: side to wall

-6’; rear to wall - 6’; control panel end to wall - 4’; top - no obstructions whatsoever; distance between adjacent units - 10’. No more than one adjacent wall may be higher than the unit.

64