York R134A manual MODEL: YCIV1220E/V, MODEL: YCIV1380E/V

Models: R134A

1 140
Download 140 pages 7.76 Kb
Page 39
Image 39
MODEL: YCIV1220E/V

FORM 201.23-EG1 (1007)

MODEL: YCIV1220E/V

AIR TEMPERATURE ON - CONDENSER (°C)

LCWT

 

25.0

 

 

30.0

 

 

35.0

 

 

40.0

 

 

45.0

 

 

46.0

 

(°C)

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

5.0

1082.7

247.9

3.9

1064.7

284.7

3.4

1044.3

326.4

3.0

1013.0

371.0

2.6

945.2

394.1

2.3

930.6

397.6

2.2

6.0

1113.5

249.6

4.0

1094.7

285.8

3.5

1073.2

327.3

3.0

1038.5

371.1

2.6

967.8

394.2

2.3

953.0

397.8

2.2

7.0

1145.0

251.6

4.1

1125.3

287.1

3.6

1102.8

328.3

3.1

1064.7

371.1

2.7

991.1

394.1

2.4

975.8

397.9

2.3

8.0

1177.1

253.9

4.2

1156.5

288.5

3.7

1133.0

329.5

3.2

1091.4

371.0

2.7

1014.9

393.9

2.4

999.0

397.7

2.4

9.0

1209.8

256.5

4.3

1188.4

290.3

3.8

1164.0

330.7

3.3

1118.6

370.9

2.8

1039.0

393.5

2.5

1022.8

397.4

2.4

10.0

1243.2

259.3

4.3

1221.0

292.3

3.8

1195.5

332.2

3.3

1146.4

370.9

2.9

1063.6

393.0

2.5

1047.0

397.0

2.5

11.0

1277.2

262.6

4.4

1254.2

294.7

3.9

1227.8

333.8

3.4

1174.3

370.9

3.0

1088.5

392.5

2.6

1071.6

396.5

2.5

12.0

1311.9

266.1

4.5

1288.1

297.2

4.0

1260.7

335.7

3.5

1201.8

370.4

3.0

1114.1

391.9

2.7

1085.7

389.4

2.6

13.0

1347.3

270.1

4.5

1322.6

300.0

4.1

1294.1

337.9

3.6

1229.8

370.1

3.1

1139.9

391.3

2.7

1095.0

379.4

2.7

MODEL: YCIV1380E/V

AIR TEMPERATURE ON - CONDENSER (°C)

LCWT

 

25.0

 

 

30.0

 

 

35.0

 

 

40.0

 

 

45.0

 

 

46.0

 

(°C)

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

5.0

1228.4

287.0

3.9

1206.7

325.4

3.4

1181.0

367.8

3.0

1146.5

415.9

2.6

1083.9

450.5

2.3

1070.4

456.8

2.2

6.0

1263.2

289.6

4.0

1241.1

327.6

3.5

1214.5

370.0

3.0

1177.1

417.5

2.6

1111.7

451.6

2.3

1097.6

457.9

2.3

7.0

1298.8

292.2

4.0

1276.1

330.0

3.5

1248.7

372.3

3.1

1208.5

419.0

2.7

1139.9

452.8

2.4

1125.5

459.0

2.3

8.0

1334.9

295.0

4.1

1311.8

332.6

3.6

1283.4

374.9

3.2

1240.5

420.6

2.8

1168.8

453.8

2.4

1153.8

460.1

2.4

9.0

1371.6

298.1

4.2

1348.0

335.4

3.7

1318.9

377.4

3.2

1273.1

422.2

2.8

1198.3

454.9

2.5

1183.0

461.2

2.4

10.0

1409.1

301.3

4.3

1384.9

338.3

3.8

1355.0

380.2

3.3

1306.1

424.0

2.9

1228.4

456.0

2.5

1205.0

457.4

2.5

11.0

1447.1

304.6

4.3

1422.5

341.3

3.8

1391.8

383.1

3.4

1339.8

425.7

2.9

1258.9

457.1

2.6

1215.9

446.2

2.6

12.0

1485.7

308.3

4.4

1460.6

344.7

3.9

1429.2

386.1

3.4

1372.9

427.0

3.0

1290.1

458.2

2.6

1226.3

435.1

2.6

13.0

1525.2

311.0

4.5

1499.4

348.1

4.0

1467.3

389.3

3.5

1406.5

428.4

3.1

1308.1

450.8

2.7

1236.0

424.3

2.7

NOTES:

 

 

1.

kWo

= Unit kW Cooling Capacity Output

2.

kWi

=

Compressor kW Input

3.

COP

= Coefficient of Performance (includes condenser fan power)

4.

LCWT

=

Leaving Chilled Water Temperature

5.Ratings based on 0.168 l/s cooler water per ton, and 0.018 (m2 – °C)/kW

6.ARI 550/590 does not provide certification for 50Hz ratings. The unique use of the YCIV variable speed drive allows compressor operation at the output speed regardless of the input power frequency. This allows for common unit/heat exchanger configurations between 60Hz and 50Hz with closely matching capacity.

JOHNSON CONTROLS

39

Page 39
Image 39
York R134A manual MODEL: YCIV1220E/V, MODEL: YCIV1380E/V