York R134A manual Temperature And Flows, SI Units

Models: R134A

1 140
Download 140 pages 7.76 Kb
Page 11
Image 11

 

 

 

 

 

 

 

 

 

FORM 201.23-EG1 (1007)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEMPERATURE AND FLOWS

 

 

 

 

 

 

 

 

(SI Units)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

LEAVING WATER

 

COOLER3 flow

AIR ON CONDENSER (°C)

 

number

TEMPERATURE (°C)

 

 

(l/s)

 

 

YCIV

 

 

 

 

 

 

 

 

 

 

MIN.1

MAX.2

 

MIN.

 

MAX.

MIN.

MAX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50 Hz

 

60 Hz

 

 

 

 

 

 

 

 

 

0600(S/P)

 

0157(S/P)

4.4

15.6

 

8.8

 

42.6

-17.8

51.7

 

0590(E/V)

 

0157(E/V)

4.4

15.6

 

10.1

 

47.3

-17.8

51.7

 

0650(S/P)

 

0177(S/P)

4.4

15.6

 

10.1

 

47.3

-17.8

51.7

 

0630(E/V)

 

0177(E/V)

4.4

15.6

 

10.1

 

47.3

-17.8

51.7

 

0720(S/P/)

 

0187(S/P)

4.4

15.6

 

10.1

 

47.3

-17.8

51.7

 

0700(E/V)

 

0187(E/V)

4.4

15.6

 

10.1

 

47.3

-17.8

51.7

 

0760(E/V)

 

0197(E/V)

4.4

15.6

 

11.4

 

47.3

-17.8

51.7

 

0770(S/P)

 

0207(S/P)

4.4

15.6

 

11.4

 

50.5

-17.8

51.7

 

0800(E/V)

 

0207(E/V)

4.4

15.6

 

11.4

 

47.3

-17.8

51.7

 

0840(S/P)

 

0227(S/P)

4.4

15.6

 

11.4

 

50.5

-17.8

51.7

 

0830(E/V)

 

0227(E/V)

4.4

15.6

 

11.4

 

47.3

-17.8

51.7

 

0920(S/P)

 

0247(S/P)

4.4

15.6

 

11.4

 

50.5

-17.8

51.7

 

0930(E/V)

 

0247(E/V)

4.4

15.6

 

10.1

 

47.3

-17.8

51.7

 

1000(S/P)

 

0267(S/P)

4.4

15.6

 

11.4

 

50.5

-17.8

51.7

 

1050(E/V)

 

0267(E/V)

4.4

15.6

 

11.4

 

50.5

-17.8

51.7

 

1070(S/P)

 

0287(S/P)

4.4

15.6

 

15.8

 

75.7

-17.8

51.7

 

1120(E/V)

 

0287(E/V)

4.4

15.6

 

15.8

 

75.7

-17.8

51.7

 

1180(S/P)

 

0307(S/P)

4.4

15.6

 

18.9

 

75.7

-17.8

51.7

 

1220(E/V)

 

0327(E/V)

4.4

15.6

 

18.9

 

75.7

-17.8

51.7

 

1340(S/P)

 

0357(S/P)

4.4

15.6

 

18.9

 

75.7

-17.8

51.7

 

1380(E/V)

 

0357(E/V)

4.4

15.6

 

18.9

 

75.7

-17.8

51.7

 

1500(S/P)

 

0397(S/P)

4.4

15.6

 

18.9

 

75.7

-17.8

51.7

 

NOTES:

1.For leaving brine temperature below 4.4°C, contact your nearest Johnson Controls office for application requirements.

2.For leaving water temperature higher than 15.6°C, contact the nearest Johnson Controls office for application guidelines.

3.The evaporator is protected against freezing to -28.8°C with an electric heater as standard.

JOHNSON CONTROLS

11

Page 11
Image 11
York R134A manual Temperature And Flows, SI Units