York R134A manual YCIV1120E/V, Dimensions – SI - continued, Johnson Controls

Models: R134A

1 140
Download 140 pages 7.76 Kb
Page 96
Image 96
YCIV1120E/V

Dimensions – SI - continued

YCIV1120E/V

 

CONTROL ENTRY

 

76 WIDE X 343 HIGH

 

38

102

POWER ENTRY

254 WIDE X 330 HIGH

VIEW B-B

44

 

Manual background 305

POWER ENTRY IS ON BOTTOM OF PANEL

Manual background C

VIEW C-C

BB

Manual background C

2238

VIEW A-A

Notes:

1.Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air patters and possible diminished performance. Johnson Controls’ unit controls will optimize the operation without nuisance high pressure safety cutouts; however, the system designer MUST consider potential performance degradation.

Access to the unit control center stipulates the unit is no higher than on spring isolators. Recommended minimum clearances: side to wall

-2m; rear to wall - 2m; control panel end to wall - 1.2m; top - no obstructions whatsoever; distance between adjacent units - 10’. No more than one adjacent wall may be higher than the unit.

96

JOHNSON CONTROLS

Page 96
Image 96
York R134A manual YCIV1120E/V, Dimensions – SI - continued, Johnson Controls